Parameter Description
1-34 Rotor Leakage Reactance (X2)
Range:
Function:
Size
[ 0.0400 -
Set the rotor leakage reactance of the
related
400.0000
motor using one of these methods:
*
Ohm]
1.
2.
3.
See Figure 3.4.
NOTICE!
1-34 Rotor Leakage Reactance (X2) will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
1-35 Main Reactance (Xh)
Range:
Function:
Size
[ 1.0000 -
Set the main reactance of the motor
related
10000.0000
using one of these methods:
*
Ohm]
1.
2.
3.
NOTICE!
1-35 Main Reactance (Xh) will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
NOTICE!
This parameter cannot be adjusted while running.
®
VLT
AQUA Drive Programming Guide
Run an AMA on a cold motor.
The adjustable frequency drive
will measure the value from the
motor.
Enter the X
value manually.
2
Obtain the value from the
motor supplier.
Use the X
default setting. The
2
adjustable frequency drive
establishes the setting on the
basis of the motor nameplate
data.
Run an AMA on a cold motor.
The adjustable frequency
drive will measure the value
from the motor.
Enter the X
value manually.
h
Obtain the value from the
motor supplier.
Use the X
default setting.
h
The adjustable frequency
drive establishes the setting
on the basis of the motor
nameplate data.
®
MG20O622 - VLT
is a registered Danfoss trademark
1-36 Iron Loss Resistance (Rfe)
Range:
Function:
Size
[ 0 -
Enter the equivalent iron loss
related
10000.000
resistance (R
*
Ohm]
for iron losses in the motor.
The R
performing an AMA.
The R
in torque control applications. If R
is unknown, leave 1-36 Iron Loss
Resistance (Rfe) on default setting.
NOTICE!
This parameter cannot be adjusted while the motor is
running.
NOTICE!
This parameter is not available from the LCP.
1-37 d-axis Inductance (Ld)
Range:
Size related
[ 0.000 - 0.000
*
mH]
NOTICE!
This parameter is only active when 1-10 Motor Construction
has the value PM, non-salient SPM [1] (Permanent Magnet
Motor).
Stator resistance and d-axis Inductance values are
normally, for asynchronous motors, described in technical
specifications as between line and common (starpoint). For
permanent magnet motors, they are typically described in
technical specifications as between Line-Line. PM motors
are typically built for star connection.
) value to compensate
Fe
value cannot be found by
Fe
value is especially important
Fe
Fe
Function:
Enter the value of the d-axis
inductance. Obtain the value from
the permanent magnet motor
data sheet.