Parameter Description
3.7.6 5-6* Pulse Outputs
Parameters for configuring the scaling and output
functions of pulse outputs. The pulse outputs are
designated for terminals 27 or 29. Select terminal 27
output in 5-01 Terminal 27 Mode and terminal 29 output in
5-02 Terminal 29 Mode.
Output value
High output
value
P 5-60(term27)
P 5-63(term29)
Figure 3.27
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
No operation
Select the operation variable assigned
for terminal 27 readouts.
NOTICE!
This parameter cannot be
adjusted while the motor is
running.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100] Output freq. 0-100
[101] Reference Min-Max
[102] Feedback +-200%
[103] Motor cur. 0-Imax
[104] Torque 0-Tlim
[105] Torque 0-Tnom
[106] Power 0-Pnom
[107] Speed 0-HighLim
[108] Torque +-160%
[109] Out frq 0-Fmax
[113] Ext. Closed-loop 1
[114] Ext. Closed-loop 2
[115] Ext. Closed-loop 3
[116] Cascade Reference
®
VLT
AQUA Drive Programming Guide
High freq.
Output
P 5-62(term27)
(Hz)
P 5-65(term29)
®
MG20O622 - VLT
is a registered Danfoss trademark
5-62 Pulse Output Max Freq #27
Range:
Function:
Set the maximum frequency for
terminal 27, corresponding to the
output variable selected in
5-60 Terminal 27 Pulse Output Variable.
5000 Hz
[0 - 32000 Hz]
*
NOTICE!
This parameter cannot be adjusted while the motor is
running.
5-63 Terminal 29 Pulse Output Variable
Select the variable for viewing on the terminal 29 display. Same
options and functions as parameter group 5-6*.
Option:
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed-loop 1
[114]
Ext. Closed-loop 2
[115]
Ext. Closed-loop 3
NOTICE!
This parameter cannot be adjusted while the motor is
running.
5-65 Pulse Output Max Freq #29
Set the maximum frequency for terminal 29 corresponding to the
output variable set in 5-63 Terminal 29 Pulse Output Variable.
Range:
5000 Hz
[0 - 32000 Hz]
*
5-66 Terminal X30/6 Pulse Output Variable
Select the variable for readout on terminal X30/6.
This parameter is active when option module MCB 101 is
installed in the adjustable frequency drive.
Same options and functions as parameter group 5-6*.
Option:
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output freq. 0-100
3
Function:
Function:
Function:
3-53
3