Troubleshooting; Warnings/Alarm Messages - Danfoss VLT AQUA Drive FC 200 Programming Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Troubleshooting

5 Troubleshooting

5.1.1 Warnings/Alarm Messages

A warning or an alarm is signalled by the relevant LED on
the front of the adjustable frequency drive and indicated
by a code on the display.
A warning remains active until its cause is no longer
present. Under certain circumstances operation of the
motor may still be continued. Warning messages may be
critical, but are not necessarily so.
In the event of an alarm, the adjustable frequency drive
will have tripped. Alarms must be reset to restart operation
once their cause has been rectified.
This may be done in three ways:
1.
By pressing [Reset].
2.
Via a digital input with the "Reset" function.
3.
Via serial communication/optional serial
communication bus.
NOTICE!
After a manual reset pressing [Reset], [Auto On] must be
pressed to restart the motor.
No.
Description
1
10 Volts low
2
Live zero error
3
No motor
4
Mains phase loss
5
DC link voltage high
6
DC link voltage low
7
DC overvoltage
8
DC undervoltage
9
Inverter overloaded
10
Motor ETR overtemperature
11
Motor thermistor overtemperature
12
Torque limit
13
Overcurrent
14
Ground Fault
15
Hardware mismatch
16
Short-circuit
®
VLT
AQUA Drive Programming Guide
If an alarm cannot be reset, the reason may be that its
cause has not been rectified, or the alarm is trip-locked
(see also Table 5.1).
Alarms that are trip-locked offer additional protection,
meaning that the line power supply must be switched off
before the alarm can be reset. After being switched back
on, the adjustable frequency drive is no longer blocked
and may be reset as described above, once the cause has
been rectified.
Alarms that are not trip-locked can also be reset using the
automatic reset function in 14-20 Reset Mode (Warning:
automatic wake-up is possible!)
If a warning and alarm is marked against a code in
Table 5.1, this means that either a warning occurs before
an alarm, or else that it is possible to specify whether it is
a warning or an alarm that is to be displayed for a given
fault.
This is possible, for instance, in 1-90 Motor Thermal
Protection. After an alarm or trip, the motor carries on
coasting, and the alarm and warning flash. Once the
problem has been rectified, only the alarm continues
flashing until the adjustable frequency drive is reset.
Warning
Alarm/Trip
X
(X)
(X)
(X)
X
X
X
X
X
(X)
(X)
X
X
X
®
MG20O622 - VLT
is a registered Danfoss trademark
Alarm/Trip Lock
(X)
(X)
(X)
X
X
X
(X)
(X)
X
X
X
X
X
X
X
X
X
5
Parameter
Reference
6-01 Live Zero Timeout
Function
1-80 Function at Stop
14-12 Function at
Mains Imbalance
1-90 Motor Thermal
Protection
1-90 Motor Thermal
Protection
5-1
5

Advertisement

Table of Contents
loading

Table of Contents