Mg20O622 - Vlt ® Is A Registered Danfoss Trademark - Danfoss VLT AQUA Drive FC 200 Programming Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description
3.7.7 5-9* Bus Controlled
This parameter group selects digital and relay outputs via
a serial communication bus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
[0 -
This parameter holds the state of the
*
2147483647 ]
digital outputs and relays that is controlled
by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is low
or inactive.
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9-15 Reserved for future terminals
Bit 16
Bit 17
Bit 18
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit
24-31
Table 3.15
5-93 Pulse Out #27 Bus Control
Range:
0 %
[0 - 100 %]
*
5-94 Pulse Out #27 Timeout Preset
Range:
0 %
[0 - 100 %]
*
5-95 Pulse Out #29 Bus Control
Range:
0 %
[0 - 100 %]
*
®
VLT
AQUA Drive Programming Guide
CC Digital Output Terminal 27
CC Digital Output Terminal 29
GPIO Digital Output Terminal X
30/6
GPIO Digital Output Terminal X
30/7
CC Relay 1 output terminal
CC Relay 2 output terminal
Option B Relay 1 output terminal
Option B Relay 2 output terminal
Option B Relay 3 output terminal
Option C Relay 1 output terminal
Option C Relay 2 output terminal
Option C Relay 3 output terminal
Option C Relay 4 output terminal
Option C Relay 5 output terminal
Option C Relay 6 output terminal
Option C Relay 7 output terminal
Option C Relay 8 output terminal
Reserved for future terminals
Function:
Function:
Function:
®
MG20O622 - VLT
is a registered Danfoss trademark
5-96 Pulse Out #29 Timeout Preset
Range:
0 %
[0 - 100 %]
*
5-97 Pulse Out #X30/6 Bus Control
Range:
0 %
[0 - 100 %]
*
5-98 Pulse Out #X30/6 Timeout Preset
Range:
0 %
[0 - 100 %]
*
Function:
3
Function:
Function:
3-55