Parameter Description
13-11 Comparator Operator
Array [6]
Option:
3
3
[0] <
[1] = (equal)
[2] >
[5] TRUE longer
than..
[6] FALSE longer
than..
[7] TRUE shorter
than..
[8] FALSE
shorter than..
13-12 Comparator Value
Array [6]
Range:
Size related
*
100000 ]
3.12.4 13-2* Timers
Use the result (TRUE or FALSE) from timers directly to
define an event (see 13-51 SL Controller Event), or as
Boolean input in a logic rule (see 13-40 Logic Rule Boolean
1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3).
A timer is only FALSE when started by an action (i.e., [29]
Start timer 1) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
3-78
Function:
Select [0] < for the result of the evaluation to
be TRUE, when the variable selected in
13-10 Comparator Operand is smaller than the
fixed value in 13-12 Comparator Value. The
result will be FALSE, if the variable selected in
13-10 Comparator Operand is greater than the
fixed value in 13-12 Comparator Value.
Select [1] ≈ for the result of the evaluation to
be TRUE, when the variable selected in
13-10 Comparator Operand is approximately
equal to the fixed value in 13-12 Comparator
Value.
Select [2] > for the inverse logic of option [0]
<.
Function:
[-100000 -
Enter the 'trigger level' for the
variable that is monitored by this
comparator. This is an array
parameter containing comparator
values 0 to 5.
MG20O622 - VLT
®
VLT
AQUA Drive Programming Guide
13-20 SL Controller Timer
Array [3]
Range:
Size related
3.12.5 13-4* Logic Rules
Combine up to three Boolean inputs (TRUE/FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT.
Select Boolean inputs for the calculation in 13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 and 13-44 Logic Rule
Boolean 3. Define the operators used to logically combine
the selected inputs in 13-41 Logic Rule Operator 1 and
13-43 Logic Rule Operator 2.
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Figure 3.36
Priority of calculation
The results of 13-40 Logic Rule Boolean 1, 13-41 Logic Rule
Operator 1 and 13-42 Logic Rule Boolean 2 are calculated
first. The outcome (TRUE/FALSE) of this calculation is
combined with the settings of 13-43 Logic Rule Operator 2
and 13-44 Logic Rule Boolean 3, yielding the final result
(TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
[0]
FALSE
[1]
TRUE
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
®
is a registered Danfoss trademark
[ 0.000 - 0.000 ]
*
Par. 13-41
Logic Rule Operator 1
. . .
. . .
Par. 13-44
Logic Rule Boolean 3
Function:
Enters the fixed value of FALSE in the
logic rule.
Enters the fixed value TRUE in the
logic rule.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
Function:
Par. 13-43
Logic Rule Operator 2
. . .
. . .