Parameter Description
Relative value
operating variable
%
100
90
80
70
60
50
40
30
20
10
Figure 3.63
Once a second, the value of the operating variable
selected is registered. If a value has been registered to
equal 13%, the counter "10% - <20%" will be updated with
the value "1". If the value stays at 13% for 10s, then "10"
will be added to the counter value.
The contents of counters can be displayed as bars on the
LCP. Select Quick Menu ⇒Loggings: Trending Continued Bin/
Trending Timed Bin/Trending Comparison.
NOTICE!
The counters starts counting whenever the adjustable
frequency drive is powered up. Power cycle shortly after a
reset will zero the counters. EEPROM data are updated
once per hour.
23-60 Trend Variable
Option:
Function:
Select the desired operating variable to be
monitored for trending.
[0] Power [kW]
Power yielded to the motor. Reference for the
relative value is the rated motor power
programmed in 1-20 Motor Power [kW] or
1-21 Motor Power [HP]. Actual value can be
read in 16-10 Power [kW] or 16-11 Power [hp].
[1] Current [A]
Output current to the motor. Reference for the
relative value is the rated motor current
programmed in 1-24 Motor Current. Actual
value can be read in 16-14 Motor current.
[2] Frequency
Output frequency to the motor. Reference for
[Hz]
the relative value is the maximum output
frequency programmed in 4-14 Motor Speed
High Limit [Hz]. Actual value can be read in
16-13 Frequency.
[3] Motor Speed
Speed of the motor. Reference for relative
[RPM]
value is the maximum motor speed
programmed in 4-13 Motor Speed High Limit
[RPM].
®
VLT
AQUA Drive Programming Guide
Counter 9: +0
0
Counter 8: +6
*
Counter 7: +2
Counter 6: +1
Counter 5: +11
Counter 4: +0
Counter 3: +1
Counter 2: +0
Counter 1: +1
Counter 0: +5
0
®
MG20O622 - VLT
is a registered Danfoss trademark
23-61 Continuous Bin Data
Range:
Function:
[0 -
Array with ten elements ([0]–[9] below
4294967295 ]
parameter number in display). Press [OK]
and step between elements using [
[
].
Ten counters with the frequency of
occurrence for the operating variable
monitored, sorted according to the following
intervals:
Counter [0]: 0%–<10%
Counter [1]: 10%–<20%
Counter [2]. 20%‒<30%
Counter [3]: 30%–<40%
Counter [4]: 40%–<50%
Counter [5]: 50%–<60%
Counter [6]. 60%‒<70%
Counter [7]: 70%–<80%
Counter [8]: 80%–<90%
Counter [9]: 90%‒<100% or Max
The above minimum limits for the intervals
are the default limits. These can be changed
in 23-65 Minimum Bin Value.
Starts to count when the adjustable
frequency drive is powered up for the first
time. All counters can be reset to 0 in
23-66 Reset Continuous Bin Data.
23-62 Timed Bin Data
Range:
Function:
[0 -
Array with ten elements ([0]–[9] below
*
4294967295 ]
parameter number in display). Press [OK]
and step between elements using [
[
].
10 counters with the frequency of
occurrence for the operating data
monitored sorted according to the intervals
as for 23-61 Continuous Bin Data.
Starts to count at the date/time
programmed in 23-63 Timed Period Start,
and stops at the time/date programmed in
23-64 Timed Period Stop. All counters can be
reset to 0 in 23-67 Reset Timed Bin Data.
3
3
] and
] and
3-143