Parameter Description
3.9 Parameters 8-** Communications and
Options
3.9.1 8-0* General Settings
3
3
8-01 Control Site
Option:
[0] Digital and
ctrl.word
[1] Digital only
[2] Controlword only
8-02 Control Source
Option:
[0]
None
[1]
FC RS-485
[2]
USB Port
[3]
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30] External Can
8-03 Control Timeout Time
Range:
Size related
*
3-62
®
VLT
Function:
The setting in this parameter overrides
the settings in 8-50 Coasting Select to
8-56 Preset Reference Select.
Control by using both digital input and
control word.
Control by using digital inputs only.
Control by using control word only.
Function:
Select the source of the control word: one of
two serial interfaces or four installed options.
During initial power-up, the adjustable
frequency drive automatically sets this
parameter to [3] Option A if it detects a valid
serial communication option installed in slot
A. If the option is removed, the serial
communication option detects a change in
the configuration, sets 8-02 Control Source
back to default setting FC Port, and the
adjustable frequency drive then trips. If an
option is installed after initial power-up, the
setting of 8-02 Control Source will not change
but the adjustable frequency drive will trip
and display: Alarm 67 Option Changed.
NOTICE!
This parameter cannot be adjusted while
the motor is running.
Function:
[1 - 18000 s]
MG20O622 - VLT
AQUA Drive Programming Guide
8-04 Control Timeout Function
Option:
[0]
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10] Select setup 4
[20] N2 Override Release
8-05 End-of-Timeout Function
Option:
[0] Hold set-up
[1] Resume set-
up
8-06 Reset Control Timeout
Option:
[0] Do not
reset
[1] Do reset Returns the adjustable frequency drive to the
®
is a registered Danfoss trademark
Function:
Select the Timeout function. The
Timeout function is activated when
the control word fails to be updated
within the time period specified in
8-03 Control Timeout Time. [20] N2
Override Release only appears after
setting the Metasys N2 protocol.
Function:
Select the action after receiving a valid control
word following a timeout. This parameter is
active only when 8-04 Control Timeout Function
is set to [7] Set-up 1, [8] Set-up 2, [9] Set-up 3 or
[10] Set-up 4.
Retains the set-up selected in 8-04 Control
Timeout Function and displays a warning, until
8-06 Reset Control Timeout toggles. Then the
adjustable frequency drive resumes its original
set-up.
Resumes the set-up active before the timeout.
Function:
This parameter is active only when the choice [0]
Hold set-up has been selected in 8-05 End-of-
Timeout Function.
Retains the set-up specified in 8-04 Control Timeout
Function, [7] Set-up 1, [8] Set-up 2, [9] Set-up 3 and
[10] Set-up 4 following a control timeout.
original set-up following a control word timeout.
When the value is set to [1] Do reset, the adjustable
frequency drive performs the reset and then
immediately reverts to the [0] Do not reset setting.