Parameter Description
[65] Reset Counter
Input for reset of counter B.
B
[66] Sleep Mode
Forces adjustable frequency drive into Sleep
Mode (see parameter group 22-4*, Sleep
Mode). Reacts on the rising edge of signal
applied!
[78] Reset
Resets all data in 16-96 Maintenance Word
Preventive
to 0.
Maintenance
Word
[80] PTC Card1
All digital inputs can be set to [80] PTC Card
1. However, only one digital input must be
set to this choice.
[85] Latched Pump
Starts deragging.
Derag
The setting options below are all related to the cascade
controller. Wiring diagrams and settings for parameter, see
parameter group 25-** for more details.
[120]
Lead Pump
Starts/stops the lead pump (controlled by
Start
the adjustable frequency drive). A start
requires that also a System Start signal has
been applied, e.g., to one of the digital
inputs set for [8] Start!
[121]
Lead Pump
Forces alternation of the lead pump in a
Alternation
cascade controller. Lead Pump Alternation,
25-50 Lead Pump Alternation must be set to
either [2] At Command or [3] At Staging or At
Command. 25-51 Alternation Event can be
set to any of the four options.
[130
Pump1
The function depends on the setting in
-
Interlock -
25-06 Number Of Pumps. If set to [0] No,
138]
Pump9
then Pump1 refers to the pump controlled
Interlock
by relay RELAY1, etc. If set to [1] Yes, Pump1
refers to the pump controlled by the
adjustable frequency drive only (without
any of the built-in relays involved) and
Pump2 to the pump controlled by the relay
RELAY1. Variable speed pump (lead) cannot
be interlocked in the basic cascade
controller.
See Table 3.13
®
VLT
AQUA Drive Programming Guide
5-10 Terminal 18 Digital Input
Option:
[8]
5-11 Terminal 19 Digital Input
Option:
[0]
5-12 Terminal 27 Digital Input
Same options and functions as parameter group 5-1*, except for
Pulse input.
Option:
[0]
[1]
[2]
[3]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
®
MG20O622 - VLT
is a registered Danfoss trademark
Setting in
parameter
group 5-1*
[130] Pump1
Interlock
[131] Pump2
Interlock
[132] Pump3
Interlock
[133] Pump4
Interlock
[134] Pump5
Interlock
[135] Pump6
Interlock
[136] Pump7
Interlock
[137] Pump8
Interlock
[138] Pump9
Interlock
Table 3.13
Function:
Start Same options and functions as parameter group 5-1*,
*
except for Pulse input.
Function:
No operation Same options and functions as parameter
*
group 5-1*, except for Pulse input.
No operation
Reset
Coast inverse
Coast and reset inv
DC brake inverse
Stop inverse
External interlock
Start
Latched start
Reverse
Start reverse
Setting in 25-06 Number Of
Pumps
[0] No
[1] Yes
Controlled
Adjustable
by RELAY1
frequency
(only if not
drive
lead pump)
controlled
(cannot be
interlocked)
Controlled
Controlled
by RELAY2
by RELAY1
Controlled
Controlled
by RELAY3
by RELAY2
Controlled
Controlled
by RELAY4
by RELAY3
Controlled
Controlled
by RELAY5
by RELAY4
Controlled
Controlled
by RELAY6
by RELAY5
Controlled
Controlled
by RELAY7
by RELAY6
Controlled
Controlled
by RELAY8
by RELAY7
Controlled
Controlled
by RELAY9
by RELAY8
Function: