Danfoss VLT AQUA Drive FC 200 Programming Manual page 73

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description
5-15 Terminal 33 Digital Input
Option:
Function:
[0]
No Operation Same options and functions as parameter
*
group 5-1* Digital Inputs.
5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
No operation This parameter is active when option module
*
MCB 101 is installed in the adjustable
frequency drive. Same options and functions
as parameter group 5-1* except for Pulse
input [32].
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
No operation This parameter is active when option module
*
MCB 101 is installed in the adjustable
frequency drive. Same options and functions
as parameter group 5-1* except for Pulse
input [32].
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
No operation This parameter is active when option module
*
MCB 101 is installed in the adjustable
frequency drive. Same options and functions
as parameter group 5-1* except for Pulse
input [32].
3.7.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in 5-01 Terminal 27 Mode and set the I/O
function for terminal 29 in 5-02 Terminal 29 Mode.
These parameters cannot be adjusted while the motor is
running.
The digital outputs can be programmed with these
functions:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control board receives supply
voltage.
[2]
Drive ready
The adjustable frequency drive is ready
for operation and applies a supply signal
on the control board.
[3]
Drive ready /
The adjustable frequency drive is ready
remote control
for operation and is in Auto On mode.
®
VLT
AQUA Drive Programming Guide
[4]
[5]
[6]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[25]
[26]
[27]
®
MG20O622 - VLT
is a registered Danfoss trademark
Stand-by / no
The adjustable frequency drive is ready
warning
for operation. No start or stop command
is been given (start/disable). There are no
warnings.
Running
Motor is running.
Running / no
The output speed is higher than the
warning
speed set in 1-81 Min Speed for Function
at Stop [RPM]. The motor is running and
there are no warnings.
Run on
Motor runs at reference speed.
reference / no
warning
Alarm
An alarm activates the output. There are
no warnings.
Alarm or
An alarm or a warning activates the
warning
output.
At torque limit
The torque limit set in 4-16 Torque Limit
Motor Mode has been exceeded.
Out of current
The motor current is outside the range
range
set in 4-18 Current Limit.
Below current,
Motor current is lower than set in
low
4-50 Warning Current Low.
Above current,
Motor current is higher than set in
high
4-51 Warning Current High.
Out of speed
Output speed is outside the range set in
range
4-52 Warning Speed Low and
4-53 Warning Speed High.
Below speed,
Output speed is lower than the setting
low
in 4-52 Warning Speed Low.
Above speed,
Output speed is higher than the setting
high
in 4-53 Warning Speed High.
Out of feedback
Feedback is outside the range set in
range
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
Below feedback
Feedback is below the limit set in
low
4-52 Warning Speed Low.
Above feedback
The feedback is above the limit set in
high
4-56 Warning Feedback Low.
Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in the
motor, the adjustable frequency drive,
the brake resistor, or the thermistor.
Reverse
Reversing. Logic '1' = relay activated, 24 V
DC when CW rotation of the motor.
Logic '0' = relay not activated, no signal,
when CCW rotation of the motor.
Bus OK
Active communication (no timeout) via
the serial communication port.
Torque limit
Used in performing a coasting stop and
and stop
in torque limit condition. If the
adjustable frequency drive has received a
stop signal and is at the torque limit, the
signal is Logic '0'.
3
3
3-47

Advertisement

Table of Contents
loading

Table of Contents