Parameter Description
6-55 Terminal 42 Output Filter
Option: Function:
The following readout analog parameters from selection
in 6-50 Terminal 42 Output have a filter selected when
6-55 Terminal 42 Output Filter is on:
Selection
Motor current (0 - I
max
Torque limit (0 - T
)
lim
Rated torque (0 - T
nom
Power (0 - P
)
nom
Speed (0 - Speed
)
max
Table 3.16
[0] Off Filter off
[1] On Filter on
3.8.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Same options and functions as 6-50 Terminal 42 Output.
Option:
[0]
No operation
*
6-61 Terminal X30/8 Min. Scale
Range:
0 %
[0 - 200 %]
*
6-62 Terminal X30/8 Max. Scale
Range:
100 %
[0 - 200 %]
*
6-63 Terminal X30/8 Output Bus Control
Range:
0 %
[0 - 100 %]
*
6-64 Terminal X30/8 Output Timeout Preset
Range:
0 %
[0 - 100 %]
*
®
VLT
AQUA Drive Programming Guide
0-20 mA
4-20 mA
)
[103]
[133]
[104]
[134]
)
[105]
[135]
[106]
[136]
[107]
[137]
Function:
Function:
Function:
Function:
Function:
®