Danfoss VLT AQUA Drive FC 200 Programming Manual page 134

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description
20-04 Feedback 2 Conversion
Option:
3
3
[0] Linear
[1] Square root
[2] Pressure to temperature
[3] Pressure to flow
[4] Velocity to flow
20-05 Feedback 2 Source Unit
See 20-02 Feedback 1 Source Unit for details.
Option:
[0]
*
20-06 Feedback 3 Source
Option:
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[15]
Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-07 Feedback 3 Conversion
Option:
[0] Linear
[1] Square root
[2] Pressure to temperature
[3] Pressure to flow
[4] Velocity to flow
20-08 Feedback 3 Source Unit
See 20-02 Feedback 1 Source Unit for details.
Option:
[0]
[1]
[5]
[10]
3-108
VLT
Function:
See 20-01 Feedback 1 Conversion for
details.
Function:
Linear
Function:
See 20-00 Feedback 1 Source for
details.
Function:
See 20-01 Feedback 1 Conversion for
details.
Function:
None
%
PPM
min
MG20O622 - VLT
®
AQUA Drive Programming Guide
20-08 Feedback 3 Source Unit
See 20-02 Feedback 1 Source Unit for details.
Option:
[11]
[12]
[20]
[21]
[22]
[23]
[24]
[25]
[30]
[31]
[32]
[33]
[34]
[40]
[41]
[45]
[60]
[70]
[71]
[72]
[73]
[74]
[75]
[80]
[120]
[121]
[122]
[123]
[124]
[125]
[126]
[127]
[130]
[131]
[132]
[140]
[141]
[145]
[160]
[170]
[171]
[172]
[173]
[174]
[180]
®
is a registered Danfoss trademark
Function:
RPM
PULSE/s
liter / sec.
liter / min
liter / hr.
m³ / sec.
m³/min
m³ / hr.
kg / sec.
kg/min
kg / hr.
ton / min
ton / hr.
m / sec.
m/min
m
°C
mbar
bar
Pa
kPa
m WG
mm Hg
kW
GPM
gal / sec.
gal/min
gal / hr.
CFM
ft³/s
ft³/min
ft³/h
lbs / sec.
lbs / min.
lbs / hr.
ft/s
ft/min
ft
°F
psi
lb/in²
in. wtr. gage
ft WG
in Hg
HP

Advertisement

Table of Contents
loading