Parameter Description
6-25 Terminal 54 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
3
3
999999.999 ]
6-26 Terminal 54 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
NOTICE!
This parameter cannot be adjusted while the motor is
running.
6-27 Terminal 54 Live Zero
Option:
[0] Disabled
[1] Enabled This parameter makes it possible to disable the
3.8.4 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range:
0.07 V
[ 0 - par. 6-31
*
V]
6-31 Terminal X30/11 High Voltage
Range:
10 V
[ par. 6-30 - 10
*
V]
3-58
Function:
Enter the analog input scaling value
that corresponds to the high
voltage/high current value set in
6-21 Terminal 54 High Voltage and
6-23 Terminal 54 High Current.
Function:
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing electrical noise in
terminal 54. A high time constant value
improves dampening but also increases
the time delay through the filter.
Function:
Live Zero monitoring and can be used, for
example, if the analog outputs are used as part of
a decentral I/O system (e.g., when not part of any
adjustable frequency drive related control
functions, but feeding an external control system
with data).
Function:
Sets the analog input scaling value to
correspond to the low reference/
feedback value (set in 6-34 Term.
X30/11 Low Ref./Feedb. Value).
Function:
Sets the analog input scaling value to
correspond to the high reference/
feedback value (set in 6-35 Term. X30/11
High Ref./Feedb. Value).
MG20O622 - VLT
®
VLT
AQUA Drive Programming Guide
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999 ]
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
100
*
999999.999 ]
6-36 Term. X30/11 Filter Time Constant
Range:
0.001 s
*
NOTICE!
This parameter cannot be adjusted while the motor is
running.
6-37 Term. X30/11 Live Zero
Option:
[0] Disabled
[1] Enabled
3.8.5 6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for
analog input 4 (X30/12) placed on option module MCB
101.
6-40 Terminal X30/12 Low Voltage
Range:
0.07 V
*
®
is a registered Danfoss trademark
Function:
Sets the analog input scaling value
to correspond to the low voltage
value (set in 6-30 Terminal X30/11
Low Voltage).
Function:
[-999999.999 -
Sets the analog input scaling value
to correspond to the high voltage
value (set in 6-31 Terminal X30/11
High Voltage).
Function:
[0.001 - 10 s] A 1
st
order digital low pass filter time
constant for suppressing electrical noise
on terminal X30/11.
Function:
This parameter makes it possible to disable the
Live Zero monitoring and can be used, for
example, if the analog outputs are used as part of
a decentral I/O system (e.g., when not part of any
adjustable frequency drive related control
functions, but feeding an external control system
with data).
Function:
[ 0 - par. 6-41
Sets the analog input scaling value to
V]
correspond to the low reference/
feedback value set in 6-44 Term. X30/12
Low Ref./Feedb. Value.