Parameter Description
8-13 Configurable Status Word STW
Option:
[65] Comparator 5
3
3
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[74] Logic Rule 4
[75] Logic Rule 5
[80] SL Digital
Output A
[81] SL Digital
Output B
[82] SL Digital
Output C
[83] SL Digital
Output D
[84] SL Digital
Output E
3-64
®
VLT
AQUA Drive Programming Guide
Function:
See parameter group 13-1*. If Comparator
5 is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See parameter group 13-4*. If Logic Rule 0
is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See parameter group 13-4*. If Logic Rule 1
is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See parameter group 13-4*. If Logic Rule 2
is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See parameter group 13-4*. If Logic Rule 3
is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See parameter group 13-4*. If Logic Rule 4
is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See parameter group 13-4*. If Logic Rule 5
is evaluated as TRUE, the output goes
high. Otherwise, it is low.
See 13-52 SL Controller Action. The output
goes high whenever the Smart Logic
Action [38] Set digital out A high is
executed. The output goes low whenever
the Smart Logic Action [32] Set digital out
A low is executed.
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [39] Set digital out B high is
executed. The input goes low whenever
the Smart Logic Action [33] Set digital out
B low is executed.
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [40] Set digital out C high is
executed. The input goes low whenever
the Smart Logic Action [34] Set digital out
C low is executed.
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [41] Set digital out D high is
executed. The input goes low whenever
the Smart Logic Action [35] Set digital out
D low is executed.
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [42] Set digital out E high is
executed. The input goes low whenever
the Smart Logic Action [36] Set digital out
E low is executed.
MG20O622 - VLT
8-13 Configurable Status Word STW
Option:
[85] SL Digital
Output F
8-14 Configurable Control Word CTW
Option:
[0] None
[1] Profile default
[2] CTW valid, active low
3.9.3 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
Protocol selection for the integrated FC
(standard) Port (RS-485) on the control card.
[0] FC
Communication according to the FC Protocol
as described in RS-485 Installation and Set-up in
the relevant Design Guide.
[1] FC MC
Same as [0] FC but to be used when
downloading SW to the adjustable frequency
drive or uploading dll file (covering information
regarding parameters available in the
adjustable frequency drive and their inter-
dependencies) to MCT 10 Set-up Software.
[2] Modbus
Communication according to the Modbus RTU
RTU
protocol.
[3] Metasys N2
[9] FC Option
8-31 Address
Range:
Size related
[ 1 - 255 ] Enter the address for the FC (standard)
*
8-32 Baud Rate
Option:
Function:
Baud rates 9600, 19200, 38400 and 76800
baud are valid for BACnet only.
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
®
is a registered Danfoss trademark
Function:
See 13-52 SL Controller Action. The input
goes high whenever the Smart Logic
Action [43] Set digital out F high is
executed. The input goes low whenever
the Smart Logic Action [37] Set digital out
F low is executed.
Function:
Selection of control word bit 10 if it is
active low or active high.
Function:
port.
Valid range: 1–126.