Introduction
1
1
1.1.7 Pulse Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [9] Latched
start
Terminal 27= 5-12 Terminal 27 Digital Input [6] Stop inverse
Terminal 37 = Safe stop (where available)
Figure 1.7
1.1.8 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = 5-10 Terminal 18 Digital Input [9]
Start (default)
Terminal 27 = 5-12 Terminal 27 Digital Input [19]
Freeze reference
Terminal 29 = 5-13 Terminal 29 Digital Input [21]
Speed up
Terminal 32 = 5-14 Terminal 32 Digital Input [22]
Slow
Terminal 29 only in FC x02 (x=series type).
1-8
®
VLT
AQUA Drive Programming Guide
Figure 1.8
1.1.9 Potentiometer Reference
Voltage reference via a potentiometer
Figure 1.9
®
MG20O622 - VLT
is a registered Danfoss trademark
12
18
27
29
32
37
Reference Source 1 = [1] Analog input 53 (default)
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Speed RPM
P 6-15
Ref. voltage
P 6-11 10 V
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
1
kΩ