Danfoss VLT AQUA Drive FC 200 Programming Manual page 83

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description
6-12 Terminal 53 Low Current
Range:
Function:
4 mA
[ 0 - par.
Enter the low current value. This reference
*
6-13 mA]
signal should correspond to the low
reference/feedback value, set in
6-14 Terminal 53 Low Ref./Feedb. Value. The
value must be set at >2 mA in order to
activate the Live Zero Timeout Function in
6-01 Live Zero Timeout Function.
6-13 Terminal 53 High Current
Range:
Function:
20 mA
[ par. 6-12 - 20
Enter the high current value
*
mA]
corresponding to the high reference/
feedback set in 6-15 Terminal 53 High
Ref./Feedb. Value.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0
[-999999.999 -
Enter the analog input scaling value
*
999999.999 ]
that corresponds to the low
voltage/low current set in
6-10 Terminal 53 Low Voltage and
6-12 Terminal 53 Low Current.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Size related
[-999999.999 - 999999.999 ]
*
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s
[0.001 - 10
Enter the time constant. This is a first-
*
s]
order digital low pass filter time constant
for suppressing electrical noise in
terminal 53. A high time constant value
improves dampening but also increases
the time delay through the filter.
NOTICE!
This parameter cannot be adjusted while the motor is
running.
6-17 Terminal 53 Live Zero
Option:
Function:
This parameter makes it possible to disable the
Live Zero monitoring and can be used, for
example, if the analog outputs are used as part of
a decentral I/O system (e.g., when not part of any
adjustable frequency drive related control
functions, but feeding an external control system
with data).
[0] Disabled
®
VLT
AQUA Drive Programming Guide
6-17 Terminal 53 Live Zero
Option:
[1] Enabled
3.8.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for
analog input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
0.07 V
6-21 Terminal 54 High Voltage
Range:
10 V
6-22 Terminal 54 Low Current
Range:
Function:
4 mA
6-23 Terminal 54 High Current
Range:
20 mA
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0
®
MG20O622 - VLT
is a registered Danfoss trademark
Function:
Function:
[ 0 - par.
Enter the low voltage value. This analog
*
6-21 V]
input scaling value should correspond to
the low reference/feedback value, set in
6-24 Terminal 54 Low Ref./Feedb. Value.
Function:
[ par. 6-20 -
Enter the high voltage value. This analog
*
10 V]
input scaling value should correspond to
the high reference/feedback value set in
6-25 Terminal 54 High Ref./Feedb. Value.
Function:
[ 0 - par.
Enter the low current value. This reference
*
6-23 mA]
signal should correspond to the low
reference/feedback value, set in
6-24 Terminal 54 Low Ref./Feedb. Value. The
value must be set at >2 mA to activate the
Live Zero Timeout Function in 6-01 Live Zero
Timeout Function.
Function:
[ par. 6-22 -
Enter the high current value
*
20 mA]
corresponding to the high reference/
feedback value set in 6-25 Terminal 54
High Ref./Feedb. Value.
Function:
[-999999.999 -
Enter the analog input scaling value
*
999999.999 ]
that corresponds to the low
voltage/low current value set in
6-20 Terminal 54 Low Voltage and
6-22 Terminal 54 Low Current.
3
3
3-57