How to Program
A 17
Figure 2.19
Main Menu/Quick Set-up is used for programming all
parameters or only the parameters in the Quick Menu (see
also description of the LCP 102 earlier in 2.3 How to
Program on the Numerical LCP).
The parameter values can be changed by pressing [
[
] when the value is flashing.
Select Main Menu by pressing [Menu] a number of times.
Select the parameter group [xx-__] and press [OK]
Select the parameter [__-xx] and press [OK]
If the parameter is an array parameter, select the array
number and press [OK]
Select the wanted data value and press [OK]
Parameters with functional choices display values such as
[1], [2], etc. For a description of the different choices, see
the individual description of the parameters in 3 Parameter
Description
[Back] for stepping backwards
[
] [
] are used for navigating between commands and
within parameters.
P 2-03
Status
Quick
Menu
Setup
Figure 2.20
®
VLT
AQUA Drive Programming Guide

2.3.1 Local Control Keys

Keys for local control are found at the bottom of the LCP.
Setup 1
] or
[Hand On] enables control of the adjustable frequency
drive via the LCP. [Hand On] also starts the motor and it is
now possible to enter the motor speed data using the
arrow keys. The key can be selected as [1] Enable or [0]
Disable via 0-40 [Hand on] Key on LCP.
External stop signals activated by means of control signals
or a serial bus will override a "start" command via the LCP.
The following control signals are still active when [Hand
On] is activated:
[Off] stops the connected motor. The key can be selected
as [1] Enable or [0] Disable via 0-41 [Off] Key on LCP.
Setup 1
If no external stop function is selected and the [Off] key is
inactive, the motor can be stopped by disconnecting the
voltage.
Main
Menu
[Auto On] enables the adjustable frequency drive to be
controlled via the control terminals and/or serial communi-
cation. When a start signal is applied on the control
terminals and/or the bus, the adjustable frequency drive
will start. The key can be selected as [1] Enable or [0]
Disable via 0-42 [Auto on] Key on LCP.
NOTICE!
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand On] [Auto On].
[Reset] is used for resetting the adjustable frequency drive
after an alarm (trip). It can be selected as [1] Enable or [0]
Disable via 0-43 [Reset] Key on LCP.
®
MG20O622 - VLT
is a registered Danfoss trademark
Hand
O
on
Figure 2.21
[Hand On] - [Off] - [Auto On]
Reset
Coasting stop inverse
Reversing
Set-up select lsb - Set-up select msb
Stop command from serial communication
Quick stop
DC brake
Auto
Reset
on