Parameter Description
8-32 Baud Rate
Option:
Function:
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
Default refers to the FC protocol.
8-33 Parity / Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol
8-30 Protocol using the FC Port. For
some of the protocols, not all options
are visible. Default depends on the
protocol selected.
[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Size related
[ 5 - 10000 ms]
*
8-36 Maximum Response Delay
Range:
Size related
[ 11 - 10001 ms]
*
8-37 Maximum Inter-Char Delay
Range:
Size related
[ 0.00 - 35.00
Specify the maximum permissible
*
ms]
time interval between receiving
two bytes. This parameter activates
timeout if transmission is
interrupted.
3.9.4 8-4* Message Selection
8-40 Telegram selection
Option:
Function:
Enables use of freely configurable
messages or standard messages for
the FC port.
[1]
Standard telegram 1
[101] PPO1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
®
VLT
AQUA Drive Programming Guide
Function:
Function:
Function:
®
MG20O622 - VLT
is a registered Danfoss trademark
8-40 Telegram selection
Option:
Function:
[107] PPO 7
[108] PPO 8
[200] Custom telegram 1
8-42 PCD Write Configuration
Option:
Function:
[0] None Select the parameters to be assigned to PCD
messages. The number of available PCDs depends on
the telegram type. The values in the PCDs will then be
written to the selected parameters as data values.
8-43 PCD Read Configuration
Option:
Function:
[0] None Select the parameters to be assigned to PCDs of the
messages. The number of available PCDs depends on
the message type. PCDs contain the actual data values
of the selected parameters.
3.9.5 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus
merging.
NOTICE!
These parameters are active only when 8-01 Control Site is
set to [0] Digital and control word.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0] Digital
Activates Start command via a digital input.
input
[1] Bus
Activates Start command via the serial communi-
cation port or serial communication option.
[2] Logic AND Activates Start command via the serial communi-
cation bus/serial communication port, AND
additionally via one of the digital inputs.
[3] Logic OR
Activates Start command via the serial communi-
cation bus/serial communication port OR via one
of the digital inputs.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the serial communi-
cation bus.
3
3
3-65