Troubleshooting
No.
Description
251
New Type Code
Table 5.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Cannot be Auto reset via 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip
will coast the motor and can be reset by pressing [Reset]
5
5
or make a reset by a digital input (parameter group 5-1*
[1]). The original event that caused an alarm cannot
damage the adjustable frequency drive or cause dangerous
conditions. A trip lock is an action when an alarm occurs,
which may damage the adjustable frequency drive or
Bit
Hex
Alarm Word Extended Status Word
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10
00000400
11
00000800
5-4
®
VLT
AQUA Drive Programming Guide
Dec
Alarm Word
Alarm Word 2
1
Brake Check (A28)
ServiceTrip, Read/
Write
2
Heatsink temp.
ServiceTrip,
(A29)
(reserved)
4
Ground Fault (A14) ServiceTrip, Type
Code/Spare Part
8
Ctrl.Card Temp
ServiceTrip,
(A65)
(reserved)
16
Ctrl. Word TO (A17) ServiceTrip,
(reserved)
32
Overcurrent (A13)
reserved
64
Torque Limit (A12)
reserved
128
Motor Th Over
reserved
(A11)
256
Motor ETR Over
reserved
(A10)
512
Inverter Overld.
reserved
(A9)
1024
DC undervolt (A8)
reserved
2048
DC overvoltage
reserved
(A7)
MG20O622 - VLT
Warning
Alarm/Trip
X
connected parts. A trip lock situation can only be reset by
power cycling.
Warning
Alarm
Trip locked
Table 5.2
Warning Word
Brake Check (W28)
Heatsink temp. (W29)
Ground Fault (W14)
Ctrl.Card Temp (W65)
Ctrl. Word TO (W17)
Overcurrent (W13)
Torque Limit (W12)
Motor Th Over (W11)
Motor ETR Over (W10)
Inverter Overld (W9)
DC undervolt (W8)
DC overvoltage (W7)
®
is a registered Danfoss trademark
Alarm/Trip Lock
Parameter
Reference
X
LED indication
yellow
flashing red
yellow and red
Warning
Extended
Word 2
Status Word
reserved
Ramping
reserved
AMA Running
reserved
Start CW/CCW
start_possible is
active, when the DI
selections [12] OR
[13] are active and
the requested
direction matches the
reference sign
reserved
Slow-down
slow-down command
active, e.g., via CTW
bit 11 or DI
Catch Up
catch up command
active, e.g., via CTW
bit 12 or DI
reserved
Feedback High
feedback > p4-57
reserved
Feedback Low
feedback < p4-56
reserved
Output Current High
current > p4-51
reserved
Output Current Low
current < p4-50
reserved
Output Freq High
speed > p4-53
Output Freq Low
speed < p4-52
Brake Check OK
brake test NOT ok