Parameter Description
10-12 Process Data Config Read
Option:
[1685] FC Port CTW 1
3
3
[1690] Alarm Word
[1691] Alarm Word 2
[1692] Warning Word
[1693] Warning Word 2
[1694] Ext. Status Word
[1695] Ext. Status Word 2
[1696] Maintenance Word
[1830] Analog Input X42/1
[1831] Analog Input X42/3
[1832] Analog Input X42/5
[1833] Analog Out X42/7 [V]
[1834] Analog Out X42/9 [V]
[1835] Analog Out X42/11 [V]
[1850] Sensorless Readout [unit]
10-13 Warning Parameter
Range:
0
[0 - 65535 ] View a DeviceNet-specific warning word. One
*
Bit
Meaning
0
Bus not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
Table 3.17
3-70
VLT
Function:
Function:
bit is assigned to every warning. Refer to the
DeviceNet Instruction Manual (MG33D) for
further information.
MG20O622 - VLT
®
AQUA Drive Programming Guide
10-14 Net Reference
Read only from LCP
Option: Function:
Select the reference source in instance 21/71 and 20/70.
[0] Off Enables reference via analog/digital inputs.
[1] On Enables reference via the serial communication bus.
10-15 Net Control
Read only from LCP
Option: Function:
Select the control source in Instance 21/71 and 20/70.
[0] Off Enables control via analog/digital inputs.
[1] On
Enable control via the serial communication bus.
3.11.3 10-2* COS Filters
10-20 COS Filter 1
Range:
0
[0 - 65535 ] Enter the value for COS Filter 1 to set up the
*
10-21 COS Filter 2
Range:
0
[0 - 65535 ] Enter the value for COS Filter 2, to set up the
*
10-22 COS Filter 3
Range:
0
[0 - 65535 ] Enter the value for COS Filter 3, to set up the
*
10-23 COS Filter 4
Range:
0
[0 - 65535 ] Enter the value for COS Filter 4 to set up the
*
®
is a registered Danfoss trademark
Function:
filter mask for the status word. When
operating in COS (Change-Of-State), this
function filters out bits in the status word that
should not be sent if they change.
Function:
filter mask for the Main Actual Value. When
operating in COS (Change-Of-State), this
function filters out bits in the Main Actual
Value that should not be sent if they change.
Function:
filter mask for PCD 3. When operating in COS
(Change-Of-State), this function filters out bits
in PCD 3 that should not be sent if they
change.
Function:
filter mask for PCD 4. When operating in COS
(Change-Of-State), this function filters out bits
in PCD 4 that should not be sent if they
change.