2.4 Initialization to Default Settings

Initialize the adjustable frequency drive to default settings
in two ways.
Recommended initialization (via 14-22 Operation Mode)
1.
Select 14-22 Operation Mode
2.
Press [OK]
3.
Select "Initialization"
4.
Press [OK]
5.
Cut off the line power supply and wait until the
display turns off.
6.
Reconnect the line power supply - the adjustable
frequency drive is now reset.
14-22 Operation Mode initializes all except:
14-50 RFI 1
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Maximum Inter-Char Delay
15-00 Operating hours to 15-05 Over Volts
15-20 Historic Log: Event to 15-22 Historic Log:
Time
15-30 Alarm Log: Error Code to 15-32 Alarm Log:
Time
Manual initialization
1.
Disconnect from the line power and wait until
the display turns off.
2.
2a
2b
3.
Release the keys after 5 s.
4.
The adjustable frequency drive is now
programmed according to default settings.
2-12
®
VLT
Press [Status] - [Main Menu] - [OK] at
the same time while powering up for
LCP 102, Graphical Display
Press [Menu] while powering up for LCP
101, Numerical Display
MG20O622 - VLT
AQUA Drive Programming Guide
This procedure initializes all except:
15-00 Operating hours
15-03 Power-ups
15-04 Over Temps
15-05 Over Volts
NOTICE!
A manual initialization also resets serial communication, RFI
filter settings (14-50 RFI 1) and fault log settings.
®