Parameter Description
14-23 Typecode Setting
Option: Function:
Use this parameter to set the type code matching the
3
3
specific adjustable frequency drive. Use this parameter
to set the type code matching the specific adjustable
frequency drive.
14-25 Trip Delay at Torque Limit
Range:
60 s
[0 - 60
*
s]
14-26 Trip Delay at Inverter Fault
Range:
Size related
*
3.13.3 14-3* Current Limit Control
The adjustable frequency drive features an integral current
limit controller which is activated when the motor current,
and thus the torque, is higher than the torque limits set in
4-16 Torque Limit Motor Mode and 4-17 Torque Limit
Generator Mode.
When the current limit is reached during motor operation
or regenerative operation, the adjustable frequency drive
will try to reduce torque below the preset torque limits as
quickly as possible without losing control of the motor.
While the current control is active, the adjustable
frequency drive can only be stopped by setting a digital
input to [2] Coast inverse or [3] Coast and reset inv. Any
signal on terminals 18 to 33 will not be active until the
adjustable frequency drive is no longer near the current
limit.
By using a digital input set to [2] Coast inverse or [3] Coast
and reset inv., the motor does not use the ramp-down
time, since the adjustable frequency drive is coasted.
3-88
Function:
Enter the torque limit trip delay in seconds.
When the output torque reaches the torque
limits (4-16 Torque Limit Motor Mode and
4-17 Torque Limit Generator Mode), a warning is
triggered. When the torque limit warning has
been continuously present for the period
specified in this parameter, the adjustable
frequency drive trips. Disable the trip delay by
setting the parameter to 60 s = OFF. Thermal
adjustable frequency drive monitoring will still
remain active.
Function:
[0 - 35 s] When the adjustable frequency drive
detects an overvoltage in the set time,
tripping will be affected after the set
time.
MG20O622 - VLT
®
VLT
AQUA Drive Programming Guide
14-30 Current Lim Ctrl, Proportional Gain
Range:
100 %
*
14-31 Current Lim Ctrl, Integration Time
Range:
Size related
14-32 Current Lim Ctrl, Filter Time
Range:
Size related
3.13.4 14-4* Energy Optimizing
Parameters for adjusting the energy optimization level in
both variable torque (VT) and automatic energy optimi-
zation (AEO) mode.
Automatic Energy Optimization is only active if 1-03 Torque
Characteristics, is set for either [2] Auto Energy Optim. CT or
[3] Auto Energy Optim. VT.
14-40 VT Level
Range:
66 %
*
NOTICE!
This parameter is not active when 1-10 Motor Construction
is set to [1] PM, non-salient SPM.
NOTICE!
This parameter cannot be adjusted while the motor is
running.
14-41 AEO Minimum Magnetization
Range:
Size related
NOTICE!
This parameter is not active when 1-10 Motor Construction
is set to [1] PM, non-salient SPM.
®
is a registered Danfoss trademark
Function:
[0 - 500 %] Enter the proportional gain value for the
current limit controller. Selection of a high
value makes the controller react faster. Too
high a setting leads to controller
instability.
[0.002 - 2 s]
*
[1 - 100 ms]
*
[40 - 90 %]
Function:
[40 - 75
Enter the minimum allowable magnet-
*
%]
ization for AEO. Selection of a low
value reduces energy loss in the
motor, but can also reduce resistance
to sudden load changes.
Function:
Function:
Function: