Parameter Description
1-91 Motor External Fan
Option: Function:
[0] No
No external fan is required, i.e., the motor is derated at
3
3
low speed.
[1] Yes Applies an external motor fan (external ventilation), so
that no derating of the motor is required at low speed.
The upper curve in graph above (fout = 1 x fM,N) is
followed if the motor current is lower than nominal
motor current (see 1-24 Motor Current). If the motor
current exceeds nominal current, the operation time still
decreases as if no fan were installed.
1-93 Thermistor Source
Option:
[0] None
[1] Analog Input 53
[2] Analog Input 54
[3] Digital input 18
[4] Digital input 19
[5] Digital input 32
[6] Digital input 33
NOTICE!
This parameter cannot be adjusted while the motor is
running.
NOTICE!
Digital input should be set to [0] PNP - Active at 24 V in
5-00 Digital I/O Mode.
3-28
®
VLT
AQUA Drive Programming Guide
Function:
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option [1] or [2] cannot be
selected if the analog input is already in
use as a reference source (selected in
3-15 Reference 1 Source, 3-16 Reference 2
Source or 3-17 Reference 3 Source ).
When using MCB 112, choice [0] None must
always be selected.