Parameter Description
Depending on the application and on the purpose of using
it, this feature can be used as preventative or reactive
measure and can be triggered/started in the following
different ways:
•
On each Start Command (29-11 Derag at Start/
Stop)
•
On each Stop Command (29-11 Derag at Start/
Stop)
•
On each Start/Stop Command (29-11 Derag at
Start/Stop)
•
On Digital Input (parameter group 5-1*)
•
On Drive Action with the Smart Logic Controller
(13-52 SL Controller Action)
•
As Timed Action (parameter group 23-**)
•
On High Power (parameter group 29-2*)
29-10 Derag Cycles
Range:
Function:
Size related
[0 - 10 ] The number of cycles the adjustable
*
frequency drive will derag.
29-11 Derag at Start/Stop
Option:
Function:
Derag function when starting and stopping
the adjustable frequency drive.
[0] Off
[1] Start
[2] Stop
[3] Start and stop
29-12 Deragging Run Time
Range:
Function:
0 s
[0 - 3600 s] The time that the adjustable frequency drive
*
will remain at the derag speed.
29-13 Derag Speed [RPM]
Range:
Size related
[ par. 4-11 - par.
*
4-13 RPM]
29-14 Derag Speed [Hz]
Range:
Size related
[ par. 4-12 - par.
*
4-14 Hz]
®
VLT
AQUA Drive Programming Guide
Function:
The speed at which the
adjustable frequency drive will
derag in RPM.
Function:
The speed at which the
adjustable frequency drive will
derag in Hertz.
®
MG20O622 - VLT
is a registered Danfoss trademark
29-15 Derag Off Delay
Range:
Function:
10 s
[1 - 600 s] The time that the adjustable frequency drive
*
will remain off before starting another derag
pulse. Allows contents of the pump to settle.
3.24.4 29-2* Derag Power Tuning
The derag feature monitors drive power in a similar
fashion as no-flow. Based on two user-defined points and
an offset value, the monitor calculates a derag power
curve. It uses the exact same calculations as No-Flow with
the difference being that derag monitors for high-power
and not low-power.
Commissioning the No-Flow user points via the No-Flow,
Auto Setup will also set the points of the derag curve to
the same value.
Power [kW/HP]
High Speed
power
Par. 29-30,
Par. 29-31
Activate Derag
Low Speed
power
Par. 29-26,
Par. 29-27
Low Speed
Par. 29-24, Par. 29-25
Figure 3.84 Derag Power Tuning
29-20 Derag Power[kW]
Range:
Function:
0 kW
[0 - 0 kW] Readout of calculated derag power at actual
*
speed.
The calculated power
+ the power factor (readout)
Par. 29-20, Par. 29-21
Derag power factor
Par. 29-22
Speed [Hz/RPM]
High Speed
Par. 29-28, Par. 29-29