Danfoss VLT AQUA Drive FC 200 Programming Manual page 60

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description
3-17 Reference 3 Source
Option:
3
3
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed-loop 1
[31] Ext. Closed-loop 2
[32] Ext. Closed-loop 3
NOTICE!
This parameter cannot be adjusted while the motor is
running.
3-19 Jog Speed [RPM]
Range:
Size
related
4-13 RPM]
*
3-34
Function:
Select the reference input to be used
for the third reference signal.
3-15 Reference 1 Source, 3-16 Reference
2 Source and 3-17 Reference 3 Source
define up to three different reference
signals. The sum of these reference
signals defines the actual reference.
Function:
[ 0 - par.
Enter a value for the jog speed n
which is a fixed output speed. The
adjustable frequency drive runs at this
speed when the jog function is
activated. The maximum limit is defined
in 4-13 Motor Speed High Limit [RPM].
See also 3-80 Jog Ramp Time.
MG20O622 - VLT
®
VLT
AQUA Drive Programming Guide
3.5.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of
the two ramps (parameter group 3-4* and parameter
group 3-5*).
Figure 3.16
3-41 Ramp 1 Ramp-up Time
Range:
Size
related
*
,
JOG
par .3 − 41 =
3-42 Ramp 1 Ramp-down Time
Range:
Size
related
*
par .3 − 42 =
®
is a registered Danfoss trademark
Function:
[ 1.00 -
Enter the ramp-up time, i.e., the
3600 s]
acceleration time from 0 RPM to
1-25 Motor Nominal Speed. Choose a
ramp-up time such that the output
current does not exceed the current
limit in 4-18 Current Limit during
ramping. See ramp-down time in
3-42 Ramp 1 Ramp-down Time.
tacc × nnom par .1 − 25
s
ref rpm
Function:
[ 1.00 -
Enter the ramp-down time, i.e., the
3600 s]
deceleration time from 1-25 Motor
Nominal Speed to 0 RPM. Choose a ramp-
down time such that no overvoltage
arises in the inverter due to regenerative
operation of the motor, and such that
the generated current does not exceed
the current limit set in 4-18 Current Limit.
See ramp-up time in 3-41 Ramp 1 Ramp-
up Time.
tdec × nnom par .1 − 25
s
ref rpm

Advertisement

Table of Contents
loading

Table of Contents