Parameter Description
16-17 Speed [RPM]
Range:
0 RPM
[-30000 - 30000 RPM]
*
16-18 Motor Thermal
Range:
Function:
0 %
[0 - 100 %] View the calculated thermal load on the
*
motor. The cut-out limit is 100%. The basis
for calculation is the ETR function selected in
1-90 Motor Thermal Protection.
16-22 Torque [%]
Range:
0 %
[-200 - 200 %]
*
3.15.2 16-3* Drive Status
16-30 DC Link Voltage
Range:
Function:
0 V
[0 - 10000 V] View a measured value. The value is filtered
*
with an 30 ms time constant.
16-32 Brake Energy /s
Range:
Function:
0 kW
[0 - 10000 kW] View the braking energy transmitted to
*
an external brake resistor, stated as an
instantaneous value.
16-33 Brake Energy /2 min
Range:
Function:
0 kW
[0 - 10000
View the braking energy transmitted to
*
kW]
an external brake resistor. The mean
power is calculated on an average basis
for the most recent 120 s.
16-34 Heatsink Temp.
Range:
0 °C
[0 - 255 °C]
*
16-35 Inverter Thermal
Range:
Function:
0 %
[0 - 100 %]
View the percentage load on the inverter.
*
16-36 Inv. Nom. Current
Range:
Size related
[0.01 - 10000 A]
*
16-37 Inv. Max. Current
Range:
Size related
[0.01 - 10000 A]
*
®
VLT
AQUA Drive Programming Guide
Function:
View the current motor RPM.
Function:
Function:
Function:
Function:
®
MG20O622 - VLT
is a registered Danfoss trademark
16-38 SL Controller State
Range:
Function:
0
[0 - 100 ] View the state of the event under execution by
*
the SL controller.
16-39 Control Card Temp.
Range:
0 °C
[0 - 100 °C]
*
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full when
15-13 Logging Mode is set to [0] Log always.
[0] No
[1] Yes
16-49 Current Fault Source
Range:
Function:
0
[0 - 8 ] Value indicates source of current fault, including:
*
short circuit, overcurrent and phase imbalance
(from left): [1-4] Inverter, [5-8] Rectifier, [0] No fault
recorded
After a short circuit alarm (I
max2
or phase imbalance), this will contain the power card
number associated with the alarm. It only holds one
number so it will indicate the highest priority power card
number (master first). The value will persist on power
cycle, but if a new alarm occurs it will be overwritten with
the new power card number (even if it a lower priority
number). The value will only be cleared when the alarm
log is cleared (e.g., a 3-finger reset would reset the readout
to 0).
3.15.3 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0
[-200 - 200 ] View the total reference, the sum of digital,
*
analog, preset, bus and freeze references, plus
catch-up and slow-down.
Function:
) or overcurrent alarm (I
max1
3-99
3
3