Parameter Description
26-00 Terminal X42/1 Mode
Option:
Function:
Terminal X42/1 can be programmed as an
analog input accepting a voltage or input from
either Pt1000 (1000 Ω at 32° F [0°C]) or Ni 1000
(1000 Ω at 32° F [0°C]) temperature sensors.
Select the desired mode.
° C] and [4] Ni 1000 [ ° C] if operating
[2] Pt 1000 [
in Celsius - [3] Pt 1000 [
operating in Fahrenheit.
NOTICE!
If the input is not in use, it must be set for
voltage!
If set for temperature and used as feedback, the
unit must be set for either Celsius or Fahrenheit
(20-12 Reference/Feedback Unit, 21-10 Ext. 1 Ref./
Feedback Unit, 21-30 Ext. 2 Ref./Feedback Unit or
21-50 Ext. 3 Ref./Feedback Unit).
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
26-01 Terminal X42/3 Mode
Option:
Function:
Terminal X42/3 can be programmed as an
analog input accepting a voltage or input from
either Pt 1000 or Ni 1000 temperature sensors.
Select the desired mode.
° C] and [4] Ni 1000 [ ° C] if operating
[2] Pt 1000 [
in Celsius - [3] Pt 1000 [
operating in Fahrenheit.
WARNING
If the input is not in use, it must be set for
voltage!
If set for temperature and used as feedback, the
unit must be set for either Celsius or Fahrenheit
(20-12 Reference/Feedback Unit, 21-10 Ext. 1 Ref./
Feedback Unit, 21-30 Ext. 2 Ref./Feedback Unit or
21-50 Ext. 3 Ref./Feedback Unit).
[1] Voltage
[2] Pt 1000
[°C]
[3] Pt 1000
[°F]
[4] Ni 1000
[°C]
®
VLT
AQUA Drive Programming Guide
° F] and [5] Ni 1000 [ ° F] if
° F] and [5] Ni 1000 [ ° F] if
®
MG20O622 - VLT
is a registered Danfoss trademark
26-01 Terminal X42/3 Mode
Option:
Function:
[5] Ni 1000
[°F]
26-02 Terminal X42/5 Mode
Option:
Function:
Terminal X42/5 can be programmed as an
analog input accepting a voltage or input from
either Pt 1000 (1000 Ω at 32° F [0°C]) or Ni
1000 (1000 Ω at 32° F [0°C]) temperature
sensors. Select the desired mode.
° C] and [4] Ni 1000 [ ° C] if operating
[2] Pt 1000 [
in Celsius - [3] Pt 1000 [
operating in Fahrenheit.
NOTICE!
If the input is not in use, it must be set for
voltage!
If set for temperature and used as feedback, the
unit must be set for either Celsius or Fahrenheit
(20-12 Reference/Feedback Unit, 21-10 Ext. 1 Ref./
Feedback Unit, 21-30 Ext. 2 Ref./Feedback Unit or
21-50 Ext. 3 Ref./Feedback Unit).
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
26-10 Terminal X42/1 Low Voltage
Range:
Function:
0.07 V
[ 0 - par.
Enter the low voltage value. This analog
*
6-31 V]
input scaling value should correspond to
the low reference/feedback value set in
26-14 Term. X42/1 Low Ref./Feedb. Value.
26-11 Terminal X42/1 High Voltage
Range:
Function:
10 V
[ par. 6-30 -
Enter the high voltage value. This analog
*
10 V]
input scaling value should correspond to
the high reference/feedback value set in
26-15 Term. X42/1 High Ref./Feedb. Value.
26-14 Term. X42/1 Low Ref./Feedb. Value
Range:
Function:
0
[-999999.999 -
Enter the analog input scaling value
*
999999.999 ]
that corresponds to the low voltage
value set in 26-10 Terminal X42/1 Low
Voltage.
3
° F] and [5] Ni 1000 [ ° F] if
3-159
3