Parameter Description
3.3.4 1-2* Motor Data
Parameter group 1-2* comprises input data from the
nameplate on the connected motor.
3
3
NOTICE!
Changing the value of these parameters affects the setting
of other parameters.
NOTICE!
1-20 Motor Power [kW], 1-21 Motor Power [HP], 1-22 Motor
Voltage and 1-23 Motor Frequency will not have effect
when 1-10 Motor Construction = [1] PM, non-salient SPM.
1-20 Motor Power [kW]
Range:
Size
[ 0.09 -
related
3000.00
*
kW]
1-21 Motor Power [HP]
Range:
Size
[ 0.09 -
related
3000.00 hp]
*
1-22 Motor Voltage
Range:
Size related
*
V]
3-18
Function:
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running. Depending
on the choices made in 0-03 Regional
Settings, either 1-20 Motor Power [kW] or
1-21 Motor Power [HP] is made invisible.
Function:
Enter the nominal motor power in HP
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
Depending on the choices made in
0-03 Regional Settings, either 1-20 Motor
Power [kW] or 1-21 Motor Power [HP] is
made invisible.
NOTICE!
This parameter cannot be adjusted
while the motor is running.
Function:
[ 10 - 1000
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds
to the nominal rated output of the
unit.
MG20O622 - VLT
®
VLT
AQUA Drive Programming Guide
NOTICE!
This parameter cannot be adjusted while the motor is
running.
1-23 Motor Frequency
Range:
Size
related
*
NOTICE!
This parameter cannot be adjusted while the motor is
running.
1-24 Motor Current
Range:
Size
related
*
NOTICE!
This parameter cannot be adjusted while the motor is
running.
1-25 Motor Nominal Speed
Range:
Size related
NOTICE!
This parameter cannot be adjusted while the motor is
running.
1-26 Motor Cont. Rated Torque
Range:
Size
related
*
®
is a registered Danfoss trademark
Function:
[20 -
Select the motor frequency value from
1000 Hz]
the motor nameplate data. For 87 Hz
operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt
4-13 Motor Speed High Limit [RPM] and
3-03 Maximum Reference to the 87 Hz
application.
Function:
[ 0.10 -
Enter the nominal motor current
10000.00 A]
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection, etc.
Function:
[100 - 60000
Enter the nominal motor speed
*
RPM]
value from the motor nameplate
data. This data is used for
calculating automatic motor
compensations.
Function:
[0.1 -
Enter the value from the motor
10000 Nm]
nameplate data. The default value
corresponds to the nominal rated
output. This parameter is available
when 1-10 Motor Construction is set to
[1] PM, non-salient SPM, i.e., the