Parameter Description
2-16 AC Brake Max. Current
Range:
100 %
[ 0 - 1000.0 %]
*
NOTICE!
2-16 AC Brake Max. Current will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
2-17 Over-voltage Control
Option:
Function:
[0]
Disabled
No OVC required.
[2]
Enabled
Activates OVC.
NOTICE!
2-17 Over-voltage Control will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
NOTICE!
The ramp time is automatically adjusted to avoid tripping
of the adjustable frequency drive.
®
VLT
AQUA Drive Programming Guide
Function:
®
MG20O622 - VLT
is a registered Danfoss trademark
3
3
3-31

Advertisement