Parameter Description
18-32 Analog Input X42/5
Range:
Function:
0
[-20 -
Readout of the value of the signal applied to
*
20 ]
terminal X42/5 on the analog I/O card (MCB
109).
The units of the value shown in the LCP will
correspond to the mode selected in
26-02 Terminal X42/5 Mode.
18-33 Analog Out X42/7 [V]
Range:
Function:
0
[0 - 30 ] Readout of the value of the signal applied to
*
terminal X42/7 on the analog I/O card (MCB 109).
The value shown reflects the selection in
26-40 Terminal X42/7 Output.
18-34 Analog Out X42/9 [V]
Range:
Function:
0
[0 - 30 ] Readout of the value of the signal applied to
*
terminal X42/9 on the analog I/O card (MCB 109).
The value shown reflects the selection in
26-50 Terminal X42/9 Output.
18-35 Analog Out X42/11 [V]
Range:
Function:
0
[0 - 30 ] Readout of the value of the signal applied to
*
terminal X42/11 on the analog I/O card (MCB
109).
The value shown reflects the selection in
26-60 Terminal X42/11 Output.
18-36 Analog Input X48/2 [mA]
Range:
Function:
0
[-20 - 20 ] View the actual current measured at input
*
X48/2 (MCB 114).
18-37 Temp. Input X48/4
Range:
Function:
0
[-500 - 500 ] View the actual temperature measured at
*
input X48/4 (MCB 114). The temperature unit
is based on the selection in 35-00 Term. X48/4
Temp. Unit.
18-38 Temp. Input X48/7
Range:
Function:
0
[-500 - 500 ] View the actual temperature measured at
*
input X48/7 (MCB 114). The temperature unit
is based on the selection in 35-02 Term. X48/7
Temp. Unit.
®
VLT
AQUA Drive Programming Guide
0
3.16.3 18-6* Inputs & Outputs 2
0
®
MG20O622 - VLT
is a registered Danfoss trademark
18-39 Temp. Input X48/10
Range:
Function:
[-500 - 500 ] View the actual temperature measured at
*
input X48/10 (MCB 114). The temperature
unit is based on the selection in 35-04 Term.
X48/10 Temp. Unit.
18-60 Digital Input 2
Range:
Function:
[0 - 65535 ] View the signal states from the active digital
*
inputs on the MCO 102 (Advanced Cascade
Controller): Counting from right to left the
positions in the binary file are: DI7...DI1 ⇒ pos.
2 ...pos. 8.
3
3
3-105