2-03 DC Brake Cut In Speed [RPM]
Range:
0 RPM*
[0 - par. 4-13 RPM]
2-04 DC Brake Cut In Speed [Hz]
Range:
0.0 Hz*
[0.0 - par. 4-14 Hz]

3.5 Main Menu - Reference/Ramps - Group 3

3.5.1 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
3-02 Minimum Reference
Range:
0 Referen-
[-999999.999 - par. 3-03 Referen-
ceFeedback-
ceFeedbackUnit]
Unit*
3-03 Maximum Reference
Range:
0 Referen-
[par. 3-02 - 999999.999 Referen-
ceFeedback-
ceFeedbackUnit]
Unit*
3-04 Reference Function
Option:
[0] *
Sum
[1]
External/Preset
Shift between external and preset via a command on a digital input.
3.5.2 3-1* References
Parameters for setting up the reference sources.
Select the preset reference(s).
Select Preset ref. bit 0 / 1 / 2
Function:
Set the DC brake cut-in speed for activation of the DC braking current set in par.2-01
Current
, upon a stop command.
Function:
Set the DC brake cut-in speed for activation of the DC braking current set in par. 2-01
Current
, upon a stop command.
Function:
Enter the Minimum Reference. The Minimum Reference is the lowest value obtainable by summing
all references. The Minimum Reference value and unit matches the configuration choice made in
par.1-00
Configuration Mode
and par. 20-12
NB!
This parameter is used in open loop only.
Function:
Enter the maximum acceptable value for the remote reference. The Maximum Reference value and
unit matches the configuration choice made in par.1-00
ence/Feedback Unit
, respectively.
NB!
If operating with par. 1-00, Configuration Mode set for Closed Loop [3], par.
20-14, Maximum Reference/Feedb. must be used.
Function:
Sums both external and preset reference sources.
Use either the preset or the external reference source.
[16], [17] or [18] for the corresponding digital inputs in parameter group 5.1*.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Reference/Feedback Unit
, respectively.
Configuration Mode
and par. 20-12
DC Brake
3
DC Brake
Refer-
57