3.4.2 Cables to the Damping Resistors 3.5 Test with the Real System Transformer and Motors 3.5.1 Re-program the Frequency Converter Parameters 3.6 On-site Final Test 3.6.1 Change Parameters to Actual 3.6.2 Run with Full Load ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 3
5.2 Parameters: 0-** Operation and Display 5.3 Parameters: 4-** Limits/Warnings 5.4 Parameters: 5-** Digital In/Out 5.5 Parameters: 7-** Controllers 5.6 Parameters: 8-** Communications and Options 5.7 Parameters: 14-** Special Functions 5.8 Parameters: 15-** AFE Information ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 4
® Contents Active Front End AFE 302 Operating Instructions Liebherr 5.9 Parameters: 16-** Data Read-outs 5.10 Parameters: 40-** Mains / Filter 5.11 Warnings/Alarm Messages Index ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Indicates a situation that may result in equipment or property-damage-only accidents. NOTE Indicates highlighted information that should be regarded with attention to avoid mistakes or operate equipment at less than optimal performance. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Printed Circuit Board Programmable Logic Controller Rated Inverter Output Current Regenerative terminals Regen Residual Current Device Revolutions Per Minute Root Mean Square Second Software Switching Mode Power Supply SMPS Synchronous Motor Speed ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
WARNING external 630V. Switch off the main switch before you dismount the front Installation in high altitudes plate. At altitudes above 2km, please contact Danfoss Drives regarding PELV. 2.1.6 System Description 2.1.3 Safety Instructions NOTE The grounded Delta or IT mains will not be used.
Page 8
One AFE centralized controller regulates and controls the three parallel power units. Control signals 560 kW 560 kW 560 kW Master Slave Slave Transformer 460 V Illustration 2.1 Active Front End Topology ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
500kW The AFE system is designed in conjunction with the Trolley motors 4x55kW @ 650V - Trolley recommended Danfoss LCL filters in which the physical size, drive 400kW power rating and electrical parameters of the filters are AFE/LCL – 1,2MW continuous, with a optimized.
Rittal TS8 enclosure. This offers a solution where the backchannel could take air from outside the facility and return the heat losses outside the facility thus reducing air- conditioning requirements. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
630V and the 400V and these transformers should be physically separated. The 400V transformer must be close to or in the E-house to have a short ground cable. NOTE Danfoss will review/evaluate the LCL filter design for each 21.5 43.4 147.1 237.5 278.9 application, especially with a new transformer used.
IGBT fasteners. See the instructions included with those replacement parts for correct values. Shaft Size Driver Size Torx/ Torque (in- Torque (Nm) lbs) T-20/7mm T-25/8mm T-30/10mm T-40/13mm T-50/17mm 18mm/19mm Table 3.2 Torque Values Table ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
AUX Relay: 240V ac 2A VSYNC: 630V 1A NOTE The control circuit including the control card terminals are isolated galvanically from the power circuit by the reinforced isolation (PELV). Illustration 3.5 Outside View ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 14
® Crane System Design Active Front End AFE 302 Operating Instructions Liebherr Illustration 3.6 Cabinet Skeleton, Inside View, and Connection View Inside the Lower Front Panel. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 15
Active Front End AFE 302 Operating Instructions Liebherr 9,10 Illustration 3.9 Cabinet Skeleton View Illustration 3.7 Outside- and Inside View Illustration 3.10 Connection View Inside the Lower Front Panel Illustration 3.8 Outside- and Inside View ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Manually close input contactor (between AFE and LCL filter). Unplug the MK105 connector on the MDCIC. Measure MK105 of MDCIC harness to the input phases. Illustration 3.13 Outside View and Cabinet Skeleton ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 17
Start checking inverters and motors. between the phases L1/L2/L3 and earth should be • Save all parameter settings with . 0V. Please call Danfoss service if you can measure a • For the crane commissioning, measure THDu and voltage greater then 10V here.
Switch Crane off. Wait at least 20s. All LCPs must be completely off. Switch Crane on. The warning 78 will disappear. Now you can run the crane with only two AFE power units. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Switch Crane on. softcharge board of the damaged power unit. The AFE runs now with all 3 power units. Disconnect the ribbon cable from the Inverter 1 position at the MDCIC. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
AFE frequency converter is different from the one in the standard frequency converter. The “Ready” signal in the AFE frequency converter is on when the DC voltage is boosted to the level within the AFE regulation range. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 21
AFE: ACtive Front End End of Start-up CC: Control Card Sequence Protection Mode PC: Power Card due to the Start-up PLC: Programmable Logic Controller Failure SC: Soft Charge Illustration 3.14 Start-up Sequence Flow Chart ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
DC voltage level is End of Stop down to zero Sequence The DC capacitor can be discharged with the external resistor, which expedites the discharge process. Illustration 3.15 Shut-down Sequence Flow Cart ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Active Front End AFE 302 Operating Instructions Liebherr 4 How to Install This chapter covers mechanical and electrical installations to and from power terminals and control card terminals. 4.1 Overall Frequency Converter Configuration Illustration 4.1 System Overview ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
When the damage is noticed, please contact the shipping company immediately to claim the damage and let Danfoss know the situation to work for the corrective action. 4.2.3 Transportation and Unpacking The following illustrations show the front and side views of the frequency converter, shipping crate, respectively.
The same principle is applied for the AFE cabinets. Illustration 4.4 1: Main Load Carrying Points 2: Main Load Carrying Points ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 26
The angle from the top of the frequency converter to the lifting cable should be 60° or greater. A spreader bar is an acceptable way to lift the F Frame. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
• Wrench with relevant metric sockets (7-17mm) of the enclosure where the frequency converter is mounted, • Extensions to wrench i.e. by using cable clamps. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Ensure that the fuses have the correct current and voltage rating. Terminal No. Function 91, 92, 93 Mains R/L1, S/L2, T/L3 Ground/Earth ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Short-circuit protection: use. The frequency converter must be protected against short- Supplementary fuses circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below to protect service Frame size Bussmann PN* Rating...
The radio interference will have been reduced. Use the fastening bolts of the devices as HF connection to the rear plate. It is necessary to remove insulating paint or similar from the fastening points. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
To remove the cable from the terminal: Insert a screw driver in the square hole. Pull out the cable. Max. 0.4 x 2.5mm 9 - 10 mm (0.37 in) ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
4-** Limits Warnings 5-** Digital inputs and outputs includes relay controls 7-** Controllers 8-** Communications and Options 14-** Special functions 15-** AFE information 16-** Data Read-Out 40-** Mains/Filter ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Select the set-up to control the frequency converter functions. Index LCP value Factory Cannot be changed. It contains the Danfoss setup data set, and can be used as a data source {1,2} when returning the other set-ups to a known {1,2} state.
Page 36
One or more warnings in a Hex code. [1693] Warning Word 2 One or more warnings in a Hex code. [1694] Ext. Status Word One or more status conditions in a Hex code. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 37
Resets the AFE without setting it in Off 0-65 Personal Menu Password and 0-66 Access to Personal without OFF mode. A password is required when Menu w/o Password will be ignored. pressing [Reset] (see [2]). ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 38
[0] then this parameter will be ignored. 0-67 Bus Password Access Range: Function: [0 - 9999 ] Writing to this parameter enables users to unlock the frequency converter from bus/ MCT10. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
40-00. 4-95 Output Voltage Deviation Timeout Range: Function: 0.001 s [0.000 - 60.000 s] Selects the max time where the voltage deviation set in par. 4-94 can be exceeded. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Set-up select bit 1 (Default Digital input 32): Same as Set- can be reset. up select bit 0 [23]. [8] Start (Default Digital input 18): Select start for a start/ stop command. Logic ‘1’ = start, logic ‘0’ = stop. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 41
Function: 0.01 s [0.01 - 600.00 This parameter makes it possible to delay the cut-out time of the relays. The selection of each mechanical relay is realised in an array parameter. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Set the wanted proportional gain of 1000.000 N/A] the DC-link voltage controller. Too large value may lead to oscillations. Power size dependent. 7-63 DC-Link PI Integral Time Range: Function: 5.0 ms [1.0 - 1.000.0 ms] ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
8-04 Control Word Timeout Function Option: Function: Stop Stop and trip 8-06 Reset Control Word Timeout Option: Function: Do not reset Do reset ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 44
Select the protocol for the FC (standard) port. Modbus RTU 8-31 Address Range: Function: Application [Application Enter the address for the FC dependent dependant] (standard) port. Valid range: 1 - 126. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 45
(digital input) and/or via the bus. NOTE This parameter is only active if par. 8-01 is set to [0] Digital and control word. Digital input Logic AND Logic OR ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Automatic reset x 3 Select Control card test [1] to test the analog Automatic reset x 4 and digital inputs and outputs and the +10 V ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 47
Select Initialization [2] to reset all parameter values to default settings, except for 15-03 Power Up's, 15-04 Over Temp's, and 15-05 Over Volt's. The frequency converter will reset during the next power-up. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Reset counter Select Reset [1] and press [OK] to reset the kWh counter to zero (see 15-02 kWh Counter). NOTE The reset is carried out by pressing [OK]. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 49
15-30 Fault Log: Error Code Array [10] Range: Function: [0 - 255 ] View the error code and look up its meaning in the Troubleshooting chapter of the FC 300 Design Guide. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 50
View the power card serial number. 5.8.5 15-9* Parameter Info 15-92 Defined Parameters Array [1000] [0 - 9999] View a list of all defined parameters in the AFE. The list ends with 0. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 51
[0.00 - 1856.00 A ] Returns the value of measured current as a mean value IRMS. 16-42 Voltage Range: Function: 0.0V [0.0 - 6000.0V] Shows the AFE output voltage when the AFE is running. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 52
View the two-byte Status word (STW) sent N/A] to the Bus-Master. Interpretation of the Status word depends on the fieldbus option installed and the Control word profile selected in 8-10 Control Profile. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 53
[0.00 - 650.00 Set the converter side mOhm] resistance of the LCL filter. 40-14 Filter Capacity Range: Function: 400 uF [0 - 65000 uF] Set the capacity of the LCL filter. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 54
14-59 Actual Number of Inverter Units Illegal PS config AFEInitialized to Default Value New spare part 14-23 Typecode Setting New Type Code Table 5.3 Alarm/Warning Code List (X) Dependent on parameter ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 55
A trip lock is an action when an alarm occurs, which may cause damage to AFE or connected units. A Trip Lock situation can only be reset by a power cycling. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
The DC bus voltage is below the undervoltage limit of the below 10V. control system. The AFE is still active. Remove some of the load from terminal 50, as the 10V supply is overloaded. Max. 15 mA or minimum 590 Ω. ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
The fault is that the frequency converter is overloaded by ALARM 38, Internal fault: more than 100% for too long. By this alarm it may be necessary to contact your Danfoss WARNING/ALARM 13, Over Current: supplier. Some possible alarm messages: The peak current limit (approx.
Some possible The external 24 V DC backup power supply may be values and reasons are listed below. overloaded, otherwise Contact your Danfoss supplier. 2314: Could not read any data from the power card WARNING 48, 1.8V supply low: EEPROM.
ALARM 247, Power card temperature This alarm is only for F Frame size units. It is equivalent to Alarm 69. The report value in the alarm log indicates which power module generated the alarm: ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 60
Control Word Timeout..............42 Fault Log: Time, 15-32................. 48 Mode, 14-20..................45 Fuses......................30 Running Hours, 15-01................. 47 Fusing....................... 31 Safety Instructions.................. 6 General Warnings................... 6 Shielded Cables..................30 Start Select, 8-53................... 44 ® MG.33.X2.02 - VLT is a registered Danfoss trademark...
Page 61
® Index Active Front End AFE 302 Operating Instructions Liebherr Trip Reset....................45 Warnings....................53 Wire Access..................... 28 ® MG.33.X2.02 - VLT is a registered Danfoss trademark...