ADAP-KOOL
Drive Programming Guide
NB!
Changing the value of these parameters affects the setting of other parameters.
1-20 Motor Power [kW]
Range:
4.00 kW*
[0.09 - 3000.00 kW]
1-21 Motor Power [HP]
Range:
4.00 hp*
[0.09 - 3000.00 hp]
1-22 Motor Voltage
Range:
500. V*
[10. - 1000. V]
1-23 Motor Frequency
Range:
50. Hz*
[20 - 1000 Hz]
NB!
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range:
7.20 A*
[0.10 - 10000.00 A]
NB!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
1420. RPM* [100 - 60000 RPM]
Function:
Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in
par.0-03
Regional Settings
, either par.1-20
invisible.
Function:
Enter the nominal motor power in HP according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in par.0-03
Motor Power [HP]
or par.1-21
is made invisible.
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Select the motor frequency value from the motor nameplate data.For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par.4-13
Maximum Reference
and par.3-03
Function:
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Motor Power [kW]
or par.1-21
Regional Settings
, either par.1-20
Motor Speed High Limit [RPM]
to the 87 Hz application.
3
Motor Power [HP]
is made
Motor Power [kW]
47