ADAP-KOOL
Drive Programming Guide
NB!
Any changes in par.4-13
in par.4-13
Motor Speed High Limit [RPM]
4-14 Motor Speed High Limit [Hz]
Range:
50/60.0
[par. 4-12 - par. 4-19 Hz]
Hz*
NB!
Max. output frequency cannot exceed 10% of the inverter switching frequency (par.14-01
4-16 Torque Limit Motor Mode
Range:
110.0 %*
[0.0 - 1000.0 %]
4-18 Current Limit
Range:
110.0 %*
[1.0 - 1000.0 %]
4-19 Max Output Frequency
Range:
100.0 Hz*
[1.0 - 1000.0 Hz]
3.6.3 4-5* Adj. Warnings
Define adjustable warning limits for current, speed, reference and feedback.
NB!
Not visible in display, only in VLT Motion Control Tool, MCT 10.
Motor Speed High Limit [RPM]
will reset the value in par.4-53
.
Function:
Enter the maximum limit for motor speed. The Motor Speed High Limit can be set to correspond to
the manufacturer's recommended maximum of the motor shaft. The Motor Speed High Limit must
exceed the in par.4-12
Motor Speed Low Limit [Hz]
par.4-12
Motor Speed Low Limit [Hz]
Menu and depending on default settings dependant on global location.
Function:
Enter the maximum torque limit for motor operation. The torque limit is active in the speed range
up to and including the rated motor speed set in par.1-25
motor from reaching the stalling torque, the default setting is 1.1 x the rated motor torque (calcu-
lated value). See also par.14-25
If a setting in par.1-00
Configuration Mode
4-16
Torque Limit Motor Mode
Function:
Enter the current limit for motor and generator operation. To protect the motor from reaching the
stalling torque, the default setting is 1.1 x the rated motor current (set in par.1-24
If a setting in par.1-00
Configuration Mode
Torque Limit Motor Mode
4-16
settings.
Function:
Enter the maximum output frequency value. par.4-19
limit on the frequency converter output frequency for improved safety in applications where acci-
dental over-speeding must be avoided. This absolute limit applies to all configurations and is
independent of the setting in par.1-00
the motor is running.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
Warning Speed High
. Only par.4-11
Motor Speed Low Limit [RPM]
will be displayed depending on other parameters in the Main
Switching Frequency
Motor Nominal Speed
Trip Delay at Torque Limit
for further details.
to par.1-28
Motor Rotation Check
is not automatically reset to the default setting.
to par.1-28
Motor Rotation Check
Current Limit
to par.4-18
are not automatically reset to the default
Max Output Frequency
Configuration Mode
. This parameter cannot be adjusted while
3 Parameter Description
to the same value as set
3
or
).
. To protect the
is changed, par.
Motor Current
).
is changed, par.
specifies the absolute
65