ADAP-KOOL
Drive Programming Guide
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-03 Reset SLC
Option:
[0] *
Do not reset SLC
[1]
Reset SLC
3.10.3 13-1* Comparators
Comparators are used for comparing continuous variables (i.e. output frequency, output current, analog input etc.) to fixed preset values. In addition,
there are digital values that will be compared to fixed time values. See explanation in par.13-10
in each scan interval. Use the result (TRUE or FALSE) directly. All parameters in this parameter group are array parameters with index 0 to 5. Select index
0 to programme Comparator 0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [5]
Option:
[0] *
DISABLED
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
[15]
Analog input AIS24V
[17]
Analog input AICCT
[18]
Pulse input FI29
[19]
Pulse input FI33
[20]
Alarm number
[30]
Counter A
[31]
Counter B
Function:
Retains programmed settings in all group 13 parameters (13-*).
Resets all group 13 parameters (13-*) to default settings.
Function:
Select the variable to be monitored by the comparator.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Comparator Operand
. Comparators are evaluated once
3
107