2 How to Programme
If [No Operation] is selected in
If [Coast Inverse] (factory default value) is selected in
Select [Changes Made] to get information about:
the last 10 changes. Use the up/down navigation keys to scroll between the last 10 changed parameters.
2
the changes made since factory setting.
Select [Loggings] to get information about the display line read-outs. The information is shown as graphs.
Only display parameters selected in par. 0-20 and par. 0-24 can be viewed. It is possible to store up to 120 samples in the memory for later reference.
Efficient Parameter Set-up for ADAP-KOOL Applications
The parameters can easily be set up for the vast majority of the ADAP-KOOL applications only by using the [Quick Setup] option.
After pressing [Quick Menu], the different choices in the Quick Menu are listed. See also illustration 6.1 below and tables Q3-1 to Q3-4 in the follow-
ing
Function Setups
section.
Example of using the Quick Setup option
Assume you want to set the Ramp Down Time to 100 seconds
1.
Select [Quick Setup]. The first
up appears
2.
Press [
] repeatedly until
appears with the default setting of 20 seconds
3.
Press [OK]
4.
Use the [
] button to highlight the 3rd digit before the comma
5.
Change '0' to '1' by using the [
6.
Use the [
] button to highlight the digit '2'
7.
Change '2' to '0' with the [
8.
Press [OK]
The new ramp-down time is now set to 100 seconds.
It is recommended to do the set-up in the order listed.
NB!
A complete description of the function is found in the
parameter sections of these Operating Instructions.
Illustration 2.6: Quick Menu view.
24
par. 5-12 Terminal 27 Digital Input
, no connection to +24 V on terminal 27 is necessary to enable start.
par. 5-12 Terminal 27 Digital Input
par. 0-01 Language
in Quick Set-
par. 3-42 Ramp 1 Ramp Down Time
] button
] button
MG.11.N1.02 - VLT
ADAP-KOOL
, a connection to +24V is necessary to enable start.
The Quick Setup menu gives access to the 13 most important setup pa-
rameters of the drive. After programming the drive will, in most cases be
ready for operation. The 13* Quick Setup parameters are shown in the
table below. A complete description of the function is given in the pa-
rameter description sections of this manual.
The display showing depends on choices made in parameter 0-02 and
0-03. The default setting of parameters 0-02 and 0-03 depends on which
region of the world the frequency converter is supplied to but can be re-
programmed as required.
Par.
Designation
0-01
Language
1-03
Torque characteristics
1-20
Motor Power
1-21
Motor Power*
1-22
Motor Voltage
1-23
Motor Frequency
1-24
Motor Current
1-25
Motor Nominal Speed
1-39
Motor Poles
4-12
Motor Speed Low Limit*
4-14
Motor Speed High Limit*
3-02
Minimum Reference
3-03
Maximum Reference
3-41
Ramp 1 Ramp up Time
3-42
Ramp 1 Ramp down Time
3-13
Reference Site
5-10
Terminal 18 Digital Input
1-29
Automatic Motor Adaptation (AMA)
Table 2.1: Quick Setup parameters
®
is a registered Danfoss trademark
®
Drive Programming Guide
[Units]
[kW]
[HP]
[V]
[Hz]
[A]
[RPM]
[Hz]
[Hz]
[s]
[s]