Danfoss ADAP-KOOL Drive Programming Manual page 96

Hide thumbs Also See for ADAP-KOOL Drive:
Table of Contents

Advertisement

3 Parameter Description
8-04 Control Timeout Function
Option:
[0] *
Off
[1]
Freeze output
3
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.8-03
Timeout Time
:
nviStartStop
nviReset Fault
nviControlWord
8-05 End-of-Timeout Function
Option:
[0]
Hold set-up
[1] *
Resume set-up
8-06 Reset Control Timeout
Option:
[0] *
Do not reset
[1]
Do reset
8-07 Diagnosis Trigger
Option:
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
96
Function:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par.8-03
after setting the N2 protocol.
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
Control Timeout Function
only when par.8-04
Retains the set-up selected in par.8-04
Reset Control Timeout
8-06
toggles. Then the frequency converter resumes its original set-up.
Resumes the set-up active prior to the time-out.
Function:
This parameter is active only when the choice
of-Timeout Function
.
Retains the set-up specified in par.8-04
control time-out.
Returns the frequency converter to the original set-up following a control word time-out. When the
Do reset
value is set to
[1], the frequency converter performs the reset and then immediately reverts
Do not reset
to the
[0] setting.
Function:
This parameter has no function for LonWorks.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
®
ADAP-KOOL
Drive Programming Guide
Control Timeout Time
. Choice [20] only appears
is set to [Set-up 1-4].
Control Timeout Function
and displays a warning, until par.
Hold set-up
[0] has been selected in par.8-05
Control Timeout Function
, [Select setup 1-4] following a
Control
End-