3 Parameter Description
22-31 Power Correction Factor
Range:
100 %*
[1 - 400 %]
22-32 Low Speed [RPM]
3
Range:
0 RPM*
[0 - par. 22-36 RPM]
22-33 Low Speed [Hz]
Range:
0 Hz*
[0.0 - par. 22-37 Hz]
22-34 Low Speed Power [kW]
Range:
0 kW*
[0.00 - 0.00 kW]
22-35 Low Speed Power [HP]
Range:
0 hp*
[0.00 - 0.00 hp]
22-36 High Speed [RPM]
Range:
0 RPM*
[0 - par. 4-13 RPM]
22-37 High Speed [Hz]
Range:
0.0 Hz*
[0.0 - par. 4-14 Hz]
22-38 High Speed Power [kW]
Range:
0 kW*
[0.00 - 0.00 kW]
174
Function:
Make corrections to the calculated power at par.22-30
If No Flow is detected, when it should not be detected, the setting should be decreased. However,
if No Flow is not detected, when it should be detected, the setting should be increased to above
100%.
Function:
Motor Speed Unit
To be used if par.0-02
Set used speed for the 50% level.
This function is used for storing values needed to tune No Flow Detection.
Function:
Motor Speed Unit
To be used if par.0-02
Set used speed for the 50% level.
The function is used for storing values needed to tune No Flow Detection.
Function:
Regional Settings
To be used if par.0-03
North America selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
Function:
Regional Settings
To be used if par.0-03
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
Function:
Motor Speed Unit
To be used if par.0-02
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
Function:
Motor Speed Unit
To be used if par.0-02
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
Function:
Regional Settings
To be used if par.0-03
North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
®
ADAP-KOOL
Drive Programming Guide
No-Flow Power
.
has been set for RPM (parameter not visible if Hz selected).
has been set for Hz (parameter not visible if RPM selected).
has been set for International (parameter not visible if
has been set for North America (parameter not visible if
has been set for RPM (parameter not visible if Hz selected).
has been set for Hz (parameter not visible if RPM selected).
has been set for International (parameter not visible if