3 Parameter Description
26-01 Terminal X42/3 Mode
Option:
3
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-02 Terminal X42/5 Mode
Option:
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-10 Terminal X42/1 Low Voltage
Range:
0.07 V*
[0.00 - par. 6-31 V]
26-11 Terminal X42/1 High Voltage
Range:
10.00 V*
[par. 6-30 - 10.00 V]
26-14 Term. X42/1 Low Ref./Feedb. Value
Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]
26-15 Term. X42/1 High Ref./Feedb. Value
Range:
100.000 N/
[-999999.999 - 999999.999 N/A]
A*
212
Function:
Terminal X42/3 can be programmed as an analog input accepting a voltage or input from either Pt
1000 or Ni 1000 temperature sensors. Select the desired mode.
Pt 1000, [2] and Ni 1000, [4] if operating in Celsius - Pt 1000, [3] and Ni 1000, [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
Feedback Unit
Ext. 3 Ref./Feedback Unit
or par.21-50
Function:
Terminal X42/5 can be programmed as an analog input accepting a voltage or input from either Pt
1000 (1000 Ω at 0° C) or Ni 1000 (1000 Ω at 0° C) temperature sensors. Select the desired mode.
Pt 1000, [2] and Ni 1000, [4] if operating in Celsius - Pt 1000, [3] and Ni 1000, [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
Reference/Feedback Unit
(par. 20-12
Feedback Unit
Ext. 3 Ref./Feedback Unit
or par.21-50
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
Term. X42/1 Low Ref./Feedb. Value
feedback value set in par.26-14
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.26-15
Function:
Enter the analog input scaling value that corresponds to the low voltage value set in par.
Terminal X42/1 Low Voltage
26-10
.
Function:
Enter the analog input scaling value that corresponds to the high voltage value set in par.
26-11
Terminal X42/1 High Voltage
.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
®
ADAP-KOOL
Drive Programming Guide
, par.21-10
Ext. 1 Ref./Feedback Unit
).
Ext. 1 Ref./Feedback Unit
, par.21-10
).
.
Term. X42/1 High Ref./Feedb. Value
, par.21-30
Ext. 2 Ref./
Ext. 2 Ref./
, par.21-30
.