Danfoss ADAP-KOOL Drive Programming Manual page 13

Hide thumbs Also See for ADAP-KOOL Drive:
Table of Contents

Advertisement

®
ADAP-KOOL
Drive Programming Guide
1.1.9 Speed Up/Down
Terminals 29/32 = Speed up/down:.
Terminal 18 Digital Input
Terminal 18 = par. 5-10
fault)
Terminal 27 Digital Input
Terminal 27 = par. 5-12
ence [19]
Terminal 29 Digital Input
Terminal 29 = par. 5-13
Terminal 32 = par. 5-14
Terminal 32 Digital Input
[22]
Note: Terminal 29 only in FC x02 (x=series type).
1.1.10 Potentiometer Reference
Voltage reference via a potentiometer:
Analog input 53
Reference Source 1 = [1]
Terminal 53, Low Voltage = 0 Volt
Terminal 53, High Voltage = 10 Volt
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Start [9] (de-
Freeze refer-
Speed up [21]
Speed down
(default)
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark