4.
Control signals from, or internally within, the frequency converter may in rare cases be activated in error, be delayed or fail to occur entirely.
When used in situations where safety is critical, e.g. when controlling the electromagnetic brake function of a hoist application, these control
signals must not be relied on exclusively.
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as
the motor connection for kinetic back up.
Systems where frequency converters are installed must, if necessary, be equipped with additional monitoring and protective devices according to the
valid safety regulations, e.g law on mechanical tools, regulations for the prevention of accidents etc. Modifications on the frequency converters by means
of the operating software are allowed.
Hoisting applications:
The frequency converter functions for controlling mechanical brakes cannot be considered as a primary safety circuit. There must always be a redundancy
for controlling external brakes.
Protection Mode
Once a hardware limit on motor current or dc-link voltage is exceeded the drive will enter "Protection mode". "Protection mode" means a change of the
PWM modulation strategy and a low switching frequency to minimize losses. This continues 10 sec after the last fault and increases the reliability and
the robustness of the drive while re-establishing full control of the motor.
In hoist applications "Protection mode" is not usable because the drive will usually not be able to leave this mode again and therefore it will extend the
time before activating the brake – which is not recommendable.
The "Protection mode" can be disabled by setting par. 14-26
of the hardware limits is exceeded.
NB!
It is recommended to disable protection mode in hoisting applications (par. 14-26
Trip Delay at Inverter Fault
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
to zero which means that the drive will trip immediately if one
Trip Delay at Inverter Fault
1 Introduction
1
= 0)
9