3 Parameter Description
3
This shows a typical Air Handling Unit (AHU). As can be seen, the addition of the Analog I/O option offers the possibility to control all of the functions
from the frequency converter, such as inlet-, return- and excaust dampers or heating/cooling coils with temperature and pressure measurements being
read by the frequency converter.
NB!
The maximum current for the analog outputs 0-10V is 1mA.
NB!
Where Live Zero Monitoring is used, it is important that any analog inputs not being used for the frequency controller, i.e. being used
as part of the Building Management System decentral I/O, should have their Live Zero function disabled.