3 Parameter Description
Function Relay
By setting par. 5-40
alarm, which could not be auto-reset. Only the relay output can be used for this; the digital outputs do not have the On Delay feature.
NB!
The motor may start without warning. If the specified number of AUTOMATIC RESETs is reached within 10 minutes, the drive enters
Manual reset [0] mode. After the Manual reset is performed, the setting of par. 14-20 reverts to the original selection. If the number
of automatic resets is not reached within 10 minutes, or when a Manual reset is performed, the internal AUTOMATIC RESET counter
returns to zero.
3
NB!
Automatic reset will also be active for resetting safe stop function in firmware version < 4.3x.
NB!
The setting in par. 14-20 is disregarded in case of Fire Mode being active (see par. 24-0*, Fire Mode).
14-21 Automatic Restart Time
Range:
10 s*
[0 - 600 s]
120
On Delay
to [9] Alarm and par. 5-41
Function:
Enter the time interval from trip to start of the automatic reset function. This parameter is active
when par. 14-20
Reset Mode
MG.11.N1.02 - VLT
ADAP-KOOL
, Relay to 40 Sec. the relay will only activate at either a trip lock alarm or an
is set to
Automatic reset
[1] - [13].
®
is a registered Danfoss trademark
®