ADAP-KOOL
Drive Programming Guide
25-46 Destaging Speed [RPM]
Option:
0 N/A
25-47 Destaging Speed [Hz]
Option:
3.19.6 25-8* Status
Readout parameters informing about the operating status of the pack controller and the compressors controlled.
Staging Speed is calculated with the following formula:
η
STAGE
%
η
= η
where n
STAGE
HIGH
100
of Staging Threshold.
Function:
Readout of the below calculated value for Destaging Speed. When removing a fixed speed com-
pressor, in order to prevent an undershoot of pressure, the variable speed compressor ramps up to
a higher speed. When the variable speed compressor reaches the "Destaging Speed" the fixed speed
compressor is destaged. Destaging Speed is calculated based on
and
Motor Speed High Limit
, par. 4-13.
Destaging Speed is calculated with the following formula:
η
DESTAGE
η
= η
DESTAGE
HIGH
100
value of Destaging Threshold.
Function:
Readout of the below calculated value for Destaging Speed. When removing a fixed speed com-
pressor, in order to prevent an undershoot of pressure, the variable speed compressor ramps up to
a higher speed. When the variable speed compressor reaches the "Destaging Speed" the fixed speed
compressor is destaged. Destaging Speed is calculated based on
Motor Speed High Limit [Hz]
and
, par. 4-14.
Destaging Speed is calculated with the following formula:
η
DESTAGE
η
= η
DESTAGE
HIGH
100
where n
is Motor Speed High Limit and n
HIGH
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
is Motor Speed High Limit and n
HIGH
Destaging Threshold
%
where n
is Motor Speed High Limit and n
HIGH
Destaging Threshold
%
is the value of Destaging Threshold.
DESTAGE100%
is the value
STAGE100%
3
, par. 25-43,
is the
DESTAGE100%
, par. 25-43,
207