Danfoss ADAP-KOOL Drive Programming Manual page 215

Hide thumbs Also See for ADAP-KOOL Drive:
Table of Contents

Advertisement

®
ADAP-KOOL
Drive Programming Guide
[139]
Bus ctrl.
[141]
Bus ctrl t.o.
26-41 Terminal X42/7 Min. Scale
Range:
0.00 %*
[0.00 - 200.00 %]
26-42 Terminal X42/7 Max. Scale
Range:
100.00 %*
[0.00 - 200.00 %]
Terminal 42 Output Max Scale
See principle graph for par.6-52
26-43 Terminal X42/7 Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
26-44 Terminal X42/7 Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
26-50 Terminal X42/9 Output
Option:
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
Function:
Scale the minimum output of the selected analog signal at terminal X42/7, as a percentage of the
maximum signal level. E.g. if a 0 V (or 0 Hz) is desired at 25% of the maximum output value. Then
programme 25%. Scaling values up to 100% can never be higher than the corresponding setting
Terminal X42/7 Max. Scale
in par.26-42
Terminal 42 Output Min Scale
See principle graph for par.6-51
Function:
Scale the maximum output of the selected analog signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output. Scale the output to give a voltage lower than 10V at
full scale; or 10V at an output below 100% of the maximum signal value. If 10V is the desired output
current at a value between 0-100% of the full-scale output, programme the percentage value in the
parameter, i.e. 50% = 10V. If a voltage between 0 and 10V is desired at maximum output, calculate
the percentage as follows:
(
)
V
10
x
desired maximum voltage
i.e.
V
10
V
5
:
× 100 % = 200 %
5
V
.
Function:
Holds the level of terminal X42/7 if controlled by bus.
Function:
Holds the preset level of terminal X42/7.
In case of a bus timeout and a timeout function is selected in par.26-50
output will preset to this level.
Function:
Set the function of terminal X42/9.
: 0 - 100 Hz, (0-20 mA)
: Minimum reference - Maximum reference, (0-20 mA)
: -200% to +200% of par. CL-14
: 0 - Torque limit (par.4-16
Torque Limit Motor Mode
: 0 - Motor rated torque, (0-20 mA)
: 0 - Motor rated power, (0-20 mA)
Motor Speed High Limit [RPM]
: 0 - Speed High Limit (par.4-13
[Hz]
), (0-20 mA)
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
.
.
100 %
Maximum Reference/Feedb.
, (0-20 mA)
), (0-20 mA)
and par.4-14
3 Parameter Description
3
Terminal X42/9 Output
the
Motor Speed High Limit
215