ADAP-KOOL
Drive Programming Guide
NB!
If one of the settings in par. 1-2* Motor Data is changed, par.1-30
parameters, will return to default setting.
This parameter cannot be adjusted while the motor is running
NB!
Full AMA should be run without filter only while reduced AMA should be run with filter.
Application Examples > Automatic Motor Adaptation
See section:
3.3.3 1-3* Adv. Motor Data
Parameters for advanced motor data. The motor data in par.1-30
to run the motor optimally. The default settings are figures based on common motor parameter values from normal standard motors. If the motor
parameters are not set correctly, a malfunction of the frequency converter system may occur. If the motor data is not known, running an AMA (Automatic
Motor Adaptation) is recommended. See the
of inertia of the rotor and the iron loss resistance (par.1-36
Par. 1-3* and par. 1-4* cannot be adjusted while the motor is running.
Illustration 3.1: Motor equivalent diagram for an asynchronous motor
1-30 Stator Resistance (Rs)
Range:
1.4000
[0.0140 - 140.0000 Ohm]
Ohm*
1-35 Main Reactance (Xh)
Range:
100.0000
[1.0000 - 10000.0000 Ohm]
Ohm*
NB!
This parameter cannot be adjusted while running.
in the Design Guide.
Stator Resistance (Rs)
Automatic Motor Adaptation
section. The AMA sequence will adjust all motor parameters except the moment
Iron Loss Resistance (Rfe)
Function:
Set the stator resistance value. Enter the value from a motor data sheet or perform an AMA on a
cold motor. This parameter cannot be adjusted while the motor is running.
Function:
Set the main reactance of the motor using one of these methods:
1.
Run an AMA on a cold motor. The frequency converter will measure the value from the
motor.
2.
Enter the X
value manually. Obtain the value from the motor supplier.
h
3.
Use the X
default setting. The frequency converter establishes the setting on the basis of
h
the motor name plate data.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
Stator Resistance (Rs)
Motor Poles
to par.1-39
Motor Poles
to par.1-39
must match the relevant motor in order
).
3 Parameter Description
, the advanced motor
3
49