ADAP-KOOL
Drive Programming Guide
14-04 PWM Random
Option:
[0] *
Off
[1]
On
3.11.3 14-1* Mains On/Off
Parameters for configuring mains failure monitoring and handling.
14-12 Function at Mains Imbalance
Option:
[0] *
Trip
[1]
Warning
[2]
Disabled
[3]
Derate
3.11.4 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation.
14-20 Reset Mode
Select the reset function after tripping. Once reset, the drive can be restarted.
Option:
[0] *
Manual reset
[1]
Automatic reset x 1
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite Automatic Reset
Application Tip:
If par. 14-20 / 14-21 is set to auto-reset after e.g. 30 Sec. this should be taken in consideration if a relay output is set to call for a service technician in
case of an alarm.
Function:
No change of the acoustic motor switching noise.
Transforms the acoustic motor switching noise from a clear ringing tone to a less noticeable 'white'
noise. This is achieved by slightly and randomly altering the synchronism of the pulse width modu-
lated output phases.
Function:
Operation under severe main imbalance conditions reduces the lifetime of the motor. Conditions are
considered severe if the motor is operated continuously near nominal load (e.g. a pump or fan
running near full speed).
When a severe mains imbalance is detected:
Trip
Select
[0] to trip the frequency converter.
Select
Warning
[1] to issue a warning.
Disabled
Select
[2] for no action.
Derate
Select
[3] for derating the frequency converter.
Function:
Manual reset
Select
[0], to perform a reset via [RESET] or via the digital inputs.
Automatic reset x 1...x20
Select
[1]-[12] to perform between one and twenty automatic resets after
tripping.
Infinite Automatic Reset
Select
[13] for continuous resetting after tripping.
MG.11.N1.02 - VLT
®