3 Parameter Description
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4 mA is needed at 0% (50% of range) - set par.6-51
Output signal 20 mA is needed at 100% (75% of range) - set par.6-52
3
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set par.6-51
Output signal 10 mA is needed at Max ref (100% of range) - set par.6-52
(20 mA / 10 mA x 100%=200%).
6-53 Terminal 42 Output Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
6-54 Terminal 42 Output Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
3.8.8 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for analog common
connection. Resolution on analog output is 12 bit.
92
Terminal 42 Output Min Scale
Terminal 42 Output Max Scale
Terminal 42 Output Min Scale
Terminal 42 Output Max Scale
Function:
Holds the level of Output 42 if controlled by bus.
Function:
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par.6-50
output will preset to this level.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
®
ADAP-KOOL
Drive Programming Guide
to 50%
to 75%
to 0%
to 200%
Terminal 42 Output