3.9.3 8-1* Ctrl. Word Settings
Parameters for configuring the option control word profile.
8-10 Control Profile
Option:
[0] *
FC profile
8-13 Configurable Status Word STW
Option:
[0]
No function
[1] *
Profile Default
3.9.4 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Protocol selection for the integrated FC (standard) Port (RS485) on the control card.
Parameter group 8-7* is only visible when FC Option [9] is chosen.
Option:
[0] *
FC
[1]
FC MC
[2]
Modbus RTU
[3]
Metasys N2
[9]
FC option
NB!
Further details can be found in the BACnet and Metasys manuals.
8-31 Address
Range:
1. N/A*
[1. - 126. N/A]
Function:
Select the interpretation of the control and status words corresponding to the installed fieldbus.
Only the selections valid for the fieldbus installed in slot A will be visible in the LCP display.
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
Function corresponds to the profile default selected in par.8-10
Function:
Communication according to the FC Protocol as described in the
RS-485 Installation and Set-up
.
FC
Same as
[0] but to be used when downloading SW to the frequency converter or uploading dll
file (covering information regarding parameters available in the frequency converter and their inter-
dependencies) to Motion Control Tool MCT10.
Communication according to the Modbus RTU protocol as described in the
chapter: RS-485 Installation and Set-up
Communication protocol. The N2 software protocol is designed to be general in nature in order to
accommodate the unique properties each device may have. Please see separate manual
Drive Metasys, MG.11.Gx.yy
.
To be used when a gateway is connected to the integrated RS-485 port, e.g. the BACnet gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and
the gateway on the network, e.g. BACnet.
VLT
®
HVAC Drive BACnet, MG.11.Dx.yy
Please see separate manual
-Baud rate for the FC port will be set to a fixed value (115.200 Baud) and
now used to set the baud rate for the network port (e.g. BACnet) on the gateway.
Function:
Enter the address for the FC (standard) port.
Valid range: 1 - 126.
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Control Profile
AKD102 Design Guide, chapter:
AKD102 Design Guide,
.
par. 8-31 Address
, is now used to set the address for
.
par. 8-32 Baud Rate
3
.
VLT
®
HVAC
, is