3.5.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of the two ramps (par. 3-4* and par. 3-5*).
3-41 Ramp 1 Ramp Up Time
Range:
10.00 s*
[1.00 - 3600.00 s]
3-42 Ramp 1 Ramp Down Time
Range:
20.00 s*
[1.00 - 3600.00 s]
3.5.4 3-5* Ramp 2
Choosing ramp parameters, see 3-4*.
3-51 Ramp 2 Ramp Up Time
Range:
10.00 s*
[1.00 - 3600.00 s]
Function:
Enter the ramp-up time, i.e. the acceleration time from 0 RPM to par.1-25
Choose a ramp-up time such that the output current does not exceed the current limit in par.
4-18
Current Limit
during ramping. See ramp-down time in par.3-42
tacc
nnorm par
×
par
.3 − 41 =
ref rpm
Function:
Enter the ramp-down time, i.e. the deceleration time from par.1-25
Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative
operation of the motor, and such that the generated current does not exceed the current limit set
in par.4-18
Current Limit
. See ramp-up time in par.3-41
tdec
×
nnorm par
par
.3 − 42 =
ref rpm
Function:
Enter the ramp-up time, i.e. the acceleration time from 0 RPM to par.1-25
Choose a ramp-up time such that the output current does not exceed the current limit in par.
4-18
Current Limit
during ramping. See ramp-down time in par.3-52
tacc
nnorm par
×
par
. 3 − 51 =
ref rpm
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Ramp 1 Ramp Down Time
.1 − 25
s
Motor Nominal Speed
Ramp 1 Ramp Up Time
.1 − 25
s
Ramp 2 Ramp Down Time
. 1 − 25
s
3
Motor Nominal Speed
.
.
to 0 RPM.
.
Motor Nominal Speed
.
.
61