Danfoss ADAP-KOOL Drive Programming Manual page 191

Hide thumbs Also See for ADAP-KOOL Drive:
Table of Contents

Advertisement

®
ADAP-KOOL
Drive Programming Guide
23-14 Maintenance Date and Time
Range:
0 N/A*
[0 - 0 N/A]
23-15 Reset Maintenance Word
Option:
[0] *
Do not reset
[1]
Do reset
NB!
When messages are reset - Maintenance Item, Action and Maintenance Date/Time are not cancelled. par.23-12
Base
is set to Disabled [0].
3.18.3 23-5* Energy Log
The frequency converter is continuously accumulating the consumption of the motor controlled, based on the actual power yielded by the frequency
converter.
These data can be used for an Energy Log function allowing the user to compare and structure the information about the energy consumption related
to time.
There are basically two functions:
-
Data related to a pre-programmed period, defined by a set date and time for start
-
Data related to a predefined period back in time e.g. last seven days within the pre-programmed period
For each of the above two functions, the data are stored in a number of counters allowing for selecting time frame and a split on hours, days or weeks.
The period/split (resolution) can be set in par.23-50
The data are based on the value registered by the kWh counter in the frequency converter. This counter value can be read in par.15-02
containing the accumulated value since the first power up or latest reset of the counter (par.15-06
All data for the Energy Log are stored in counters which can be read from par.23-53
Function:
Set the date and time for next maintenance occurrence if the Preventive Maintenance Event is based
on date/time. Date format depends on the setting in par.0-71
depends on the setting in par.0-72
NB!
The frequency converter has no back up of the clock function and the set date/
time will reset to default (2000-01-01 00:00) after a power down. In par.
Clock Fault
0-79
been set properly, e.g. after a power down.
The time set must be at least one hour from the actual time!
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date
and time is included.
Function:
Do reset
Set this parameter to
[1] to reset the Maintenance Word in par.16-96
and reset the message displayed in the LCP. This parameter will change back to
when pressing OK.
Energy Log Resolution
.
Energy Log
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Date Format
Time Format
.
it is possible to program for a Warning in case the clock has not
Reset kWh Counter
).
.
while the time format
3
Maintenance Word
Do not reset
[0]
Maintenance Time
kWh Counter
191